Date |
Text |
2016-01-22 13:13:02 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| 1. THE APPLICABLE EDITION OF THE NEC IS THE 2011, AS |
| REFERENCED IN THE 5TH EDITION OF THE FBC-2014. CORRECT |
| ELECTRICAL LIGHTING SITE KEY NOTE 5. |
| 2. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS |
| PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL |
| INSPECTOR. NO SITE TUBES WILL BE ACCEPTED |
| 3. PROTECTION SHALL BE PROVIDED AT THE ENDS OF THE |
| UNI-STRUT. END CAPS REQUIRED. |
| 4. PHYSICAL PROTECTION FOR THE RACK AS DESCRIBED IN NEC |
| 110.27(B) SHALL BE PROVIDED. |
| 5. PROVIDE A LIGHT DENSITY ALLOWANCE CHART AS PER |
| FBC-EC405.6.2; THIS SHALL INCLUDE EXISTING LIGHTING IN |
| ADDITION TO THE PROPOSED. |
| 6. PROVIDE SPECS FOR THE PROPOSED SIGNS. |
| 7. NEC 408.4 REQUIRES A CIRCUIT DIRECTORY, THE SIGN |
| CIRCUITS DO NOT APPEAR ON THE PANEL SCHEDULE. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE |
| NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |