Plan Review Notes For Permit 16010443
Permit Number 16010443
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-22 13:13:02THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE APPLICABLE EDITION OF THE NEC IS THE 2011, AS
 REFERENCED IN THE 5TH EDITION OF THE FBC-2014. CORRECT
 ELECTRICAL LIGHTING SITE KEY NOTE 5.
 2. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS
 PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL
 INSPECTOR. NO SITE TUBES WILL BE ACCEPTED
 3. PROTECTION SHALL BE PROVIDED AT THE ENDS OF THE
 UNI-STRUT. END CAPS REQUIRED.
 4. PHYSICAL PROTECTION FOR THE RACK AS DESCRIBED IN NEC
 110.27(B) SHALL BE PROVIDED.
 5. PROVIDE A LIGHT DENSITY ALLOWANCE CHART AS PER
 FBC-EC405.6.2; THIS SHALL INCLUDE EXISTING LIGHTING IN
 ADDITION TO THE PROPOSED.
 6. PROVIDE SPECS FOR THE PROPOSED SIGNS.
 7. NEC 408.4 REQUIRES A CIRCUIT DIRECTORY, THE SIGN
 CIRCUITS DO NOT APPEAR ON THE PANEL SCHEDULE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  