Plan Review Notes
Plan Review Notes For Permit 16010345
Permit Number 16010345
Review Stop P
Sequence Number 1
Notes
Date Text
2016-01-16 07:26:091) THE ENGINEERING FOR THE GAS HEATER ANCHORING IS
 BASED ON THE 2010 FBC. THE CODE IN EFFECT IS THE 2014
 FBC.
 2) THE ENGINEERING DOCUMENT FOR THE POOL HEATER
 ANCHORING IS A COPY OF ANORIGINAL SIGNED AND SEALED
 DOCUMENT. F.A.C. RULE 61G15-23.001 REQUIRES DOCUMENTS
 PREPARED BY THE DESIGNER TO BEAR THE SEAL AND SIGNATURE
 OF THE ENGINEER OF RECORD.SUBMIT THE REQUIRED SIGNED
 AND SEALED DOCUMENT FOR REVIEW. THE ENGINEER FOR THE
 WIND DESIGN IS DIFFERENT THAN THE ENGINEER FOR THE POOL
 DESIGN. CLARIFY.ALSO, CHECK THE EXPOSURE. IT IS CALLED
 OUT AS EXPOSSURE D.
 3) THE LOCATION OF THE POOL EQUIPMENT ON THE POOL PLAN
 DOES NOT CORRELATE WITH THE POOL PLAN. CLARIFY.
 4) R403.9.2 TIME SWITCHES.
 TIME SWITCHES OR OTHER CONTROL METHOD THAT CAN
 AUTOMATICALLY TURN OFF AND ON HEATERS AND PUMPS
 ACCORDING TO A PRESET SCHEDULE SHALL BE INSTALLED ON
 ALL HEATERS AND PUMPS. HEATERS, PUMPS AND MOTORS THAT
 HAVE BUILT IN TIMERS SHALL BE DEEMED IN COMPLIANCE WITH
 THIS REQUIREMENT.
 5) R403.9.3 COVERS.
 HEATED SWIMMING POOLS AND INGROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
  