Plan Review Notes
Plan Review Notes For Permit 16010338
Permit Number 16010338
Review Stop B
Sequence Number 2
Notes
Date Text
2016-03-16 18:01:25APPROVED WITH EXCEPTION
  
 THE COMPONENT AND CLADDING PRESSURES SPECIFIED ON THE
 PLANS FOR THE 16' X 8' GARAGE DOOR ARE HIGHER THAN THE
 DESIGN PRESSURES IN THE NOA FOR THE GARAGE DOOR. THE
 PRESSURES ON THE PLAN APPEAR TO BE TOO HIGH FOR A
 SECTIONAL GARAGE DOOR. REVISE THE PRESSURES ON PLAN
 SHEET A-3 OR SUBMIT PRODUCT APPROVALS WITH GREATER
 DESIGN PRESSURES. FBC-R301.2.1
  
 THE PRE-REMODEL ELEVATION CERTIFICATE THAT WAS
 SUBMITTED DATED 3/1/16 IS ON THE OLD FORM AND IS
 EXPIRED. THE NEW FORMS WHICH EXPIRE ON 11/30/2018
 BECAME EFFECTIVE ON 1/9/2016. SUBMIT ELEVATION
 CERTIFICATES USING THE NEW FORMS.