Plan Review Notes
Plan Review Notes For Permit 16010338
Permit Number 16010338
Review Stop P
Sequence Number 1
Notes
Date Text
2016-01-28 05:01:011) THE LAVATORIES IN THE MASTER BATH ARE NOT VENTED.
 2014 FBCR SEC.P3101.2.
 2) A VENT IS REQD. BETWEEN THE TUB & SHOWER IN THE
 MASTER BATH. 2014 FBCR SEC.P3101.2.
 3) BATH #2 - A VENT IS REQUIRED BETWEEN THE WATER
 CLOSET AND THE SHOWER. 2014 FBCR SEC.P3101.2.
 4) BATH #3 - A VENT IS REQUIRED BETWEEN THE WATER
 CLOSET AND THE SHOWER. 2014 FBCR SEC.P3101.2.
 5) A VENT IS REQUIRED ON THE WASHING MACHINE. 2014 FBCR
 SEC.P3101.2.
 6) THE WASHING MACHINE AND LAVATORY CANNOT DISCHARGE
 INTO THE WASTE STACK AT THE SAME LEVEL PER 2014 FBCR
 SEC.P3005.1.1.
 7) CLEANOUTS ARE REQUIRED IN THE BASE OF SOIL % WASTE
 STACKS PER 2014 FBCR SEC. P3005.2.6.
 8) SEPARATE PLANS AND PERMIT ARE REQUIRED FOR THE GAS
 PIPING INSTALLATION.
  