Plan Review Notes
Plan Review Notes For Permit 16010338
Permit Number 16010338
Review Stop B
Sequence Number 1
Notes
Date Text
2016-02-11 11:09:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA. THE PROPOSED WORK IS AN ADDITION AND SUBSTANTIAL
 IMPROVEMENT TO THE EXISTING STRUCTURE. THE CITY OF WEST
 PALM BEACH'S FLOOD ORDINANCE, FEMA AND THE 2014 FLORIDA
 BUILDING CODE RESIDENTIAL REQUIRE THE STRUCTURE TO
 COMPLY WITH THE FLOOD ORDINANCE. THE MINIMUM FINISH
 FLOOR ELEVATION IS REQUIRED TO BE 7.5' NGVD 1929.
 SPECIFY THE FINISH FLOOR ELEVATIONS ON THE PLANS BASED
 ON NGVD 1929 AND SUBMIT A PRECONSTRUCTION ELEVATION
 CERTIFICATE.
  
 2) A SEPARATE PERMIT, APPLICATION AND PLANS ARE
 REQUIRED FOR THE ELECTRIC GENERATOR. FBC 105.1
  
 3) THE COMPONENT AND CLADDING PRESSURES ON SHEETS A-3
 ARE INCORRECT FOR THE SECTIONAL GARAGE DOOR AND FRENCH
 DOORS ON THE PROPOSED WEST ELEVATION. BASED ON FBCR
 TABLES R301.2(2), R301.2(3) AND R301.2(4) THE SPECIFIED
 PRESSURES ARE LOWER THAN REQUIRED.
  
 4) THE DOOR SCHEDULE ON A-7 SPECIFIES A GLASS PANEL ON
 TOP OF THE ENTRY DOOR, BUT NOT SIDELITES ON EACH SIDE
 AS SHOWN ON THE FLOOR PLAN AND ELEVATIONS ON SHEETS A-1
 AND A-3. PLEASE CLARIFY. SPECIFY THE SIZES OF THE
 SIDELITES AND THE TRANSOM ON THE PLANS. FBC 107.2.1
  
 5) ON SHEET S-2 ROOF FRAMING NOTE #6 REFERENCES THE
 2010 FBC AND THE 2014 FBC SHOULD BE REFERENCED.
  
 6) ON SHEET E-1 THE GENERAL ELECTRICAL NOTES REFERENCES
 THE 2008 NEC AND THE 2011 NEC SHOULD BE REFERENCED.
  
 7) THE WINDOW SCHEDULE ON SHEET A-7 SPECIFIES DOUBLE
 HUNG WINDOWS AND THE PRODUCT APPROVALS THAT WERE
 SUBMITTED ARE FOR SINGLE HUNG WINDOWS. PLEASE CLARIFY.
 FBC 107.2.1
  
 8) THE PLANS SPECIFY DOUBLE OUTSWING WOOD FRENCH DOORS
 WITH AND WITHOUT SIDELITES. THE PRODUCT APPROVALS THAT
 WERE SUBMITTED ARE FOR SINGLE OUTSWING ALUMINUM FRENCH
 DOORS W/WO SIDELITES. SUBMIT PRODUCT APPROVALS FOR THE
 DOORS THAT WILL BE USED. FBC 107.2.1 & DCA RULE 9N-72
  
 9) SUBMIT TWO SETS OF THE CURRENT ICC-ES EVALUATION
 REPORTS FOR THE SPRAY FOAM INSULATION THAT WILL BE
 INSTALLED. FBC-R316
  
 10) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS,
 LISTING AND INSTALLATION INSTRUCTIONS FOR THE FACTORY
 BUILT GAS FIREPLACE AND CHIMNEY. FBC-R1005
  
 11) PROVIDE STRUCTURAL DETAILS FOR THE FIREPLACE AND
 CHIMNEY. FBC 107.2.1
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.