2016-02-11 11:09:24 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD |
| AREA. THE PROPOSED WORK IS AN ADDITION AND SUBSTANTIAL |
| IMPROVEMENT TO THE EXISTING STRUCTURE. THE CITY OF WEST |
| PALM BEACH'S FLOOD ORDINANCE, FEMA AND THE 2014 FLORIDA |
| BUILDING CODE RESIDENTIAL REQUIRE THE STRUCTURE TO |
| COMPLY WITH THE FLOOD ORDINANCE. THE MINIMUM FINISH |
| FLOOR ELEVATION IS REQUIRED TO BE 7.5' NGVD 1929. |
| SPECIFY THE FINISH FLOOR ELEVATIONS ON THE PLANS BASED |
| ON NGVD 1929 AND SUBMIT A PRECONSTRUCTION ELEVATION |
| CERTIFICATE. |
| |
| 2) A SEPARATE PERMIT, APPLICATION AND PLANS ARE |
| REQUIRED FOR THE ELECTRIC GENERATOR. FBC 105.1 |
| |
| 3) THE COMPONENT AND CLADDING PRESSURES ON SHEETS A-3 |
| ARE INCORRECT FOR THE SECTIONAL GARAGE DOOR AND FRENCH |
| DOORS ON THE PROPOSED WEST ELEVATION. BASED ON FBCR |
| TABLES R301.2(2), R301.2(3) AND R301.2(4) THE SPECIFIED |
| PRESSURES ARE LOWER THAN REQUIRED. |
| |
| 4) THE DOOR SCHEDULE ON A-7 SPECIFIES A GLASS PANEL ON |
| TOP OF THE ENTRY DOOR, BUT NOT SIDELITES ON EACH SIDE |
| AS SHOWN ON THE FLOOR PLAN AND ELEVATIONS ON SHEETS A-1 |
| AND A-3. PLEASE CLARIFY. SPECIFY THE SIZES OF THE |
| SIDELITES AND THE TRANSOM ON THE PLANS. FBC 107.2.1 |
| |
| 5) ON SHEET S-2 ROOF FRAMING NOTE #6 REFERENCES THE |
| 2010 FBC AND THE 2014 FBC SHOULD BE REFERENCED. |
| |
| 6) ON SHEET E-1 THE GENERAL ELECTRICAL NOTES REFERENCES |
| THE 2008 NEC AND THE 2011 NEC SHOULD BE REFERENCED. |
| |
| 7) THE WINDOW SCHEDULE ON SHEET A-7 SPECIFIES DOUBLE |
| HUNG WINDOWS AND THE PRODUCT APPROVALS THAT WERE |
| SUBMITTED ARE FOR SINGLE HUNG WINDOWS. PLEASE CLARIFY. |
| FBC 107.2.1 |
| |
| 8) THE PLANS SPECIFY DOUBLE OUTSWING WOOD FRENCH DOORS |
| WITH AND WITHOUT SIDELITES. THE PRODUCT APPROVALS THAT |
| WERE SUBMITTED ARE FOR SINGLE OUTSWING ALUMINUM FRENCH |
| DOORS W/WO SIDELITES. SUBMIT PRODUCT APPROVALS FOR THE |
| DOORS THAT WILL BE USED. FBC 107.2.1 & DCA RULE 9N-72 |
| |
| 9) SUBMIT TWO SETS OF THE CURRENT ICC-ES EVALUATION |
| REPORTS FOR THE SPRAY FOAM INSULATION THAT WILL BE |
| INSTALLED. FBC-R316 |
| |
| 10) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS, |
| LISTING AND INSTALLATION INSTRUCTIONS FOR THE FACTORY |
| BUILT GAS FIREPLACE AND CHIMNEY. FBC-R1005 |
| |
| 11) PROVIDE STRUCTURAL DETAILS FOR THE FIREPLACE AND |
| CHIMNEY. FBC 107.2.1 |
| |
| 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |