Plan Review Notes For Permit 16010280 |
Permit Number |
16010280 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-19 09:12:16 | PERMIT #16010280 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | APPROVED PROVISO WITH COMMENTS: | | 1) KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO | | THE BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL | | FIRE ALARM CONDITION. | | | | 2) DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE | | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE | | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT | | TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE | | SURFACE. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 804-4751 | | |
|