Plan Review Notes
Plan Review Notes For Permit 16010225
Permit Number 16010225
Review Stop B
Sequence Number 8
Notes
Date Text
2018-04-06 18:18:13 
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE ENERGY CALCULATIONS SUBMITTED TO MATCH
 PLANS.; A) CONDITIONED FLOOR AREA. B) FLOOR AREAS. C)
 ROOF MATERIAL. D) TAKING CEILING FAN CREDIT. PROVIDE
 FANS SIZES REQ'D BY SEC. R405.7.6 FBC ENERGY
 CONSERVATION. E) REVISE ATTIC VENT RATIO OF 1/300. SEE
 SEC. R806.2 OF THE FBC-RESIDENTIAL.
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED.
2018-04-06 18:17:4304/06/18 MET WITH MR. ERNEST (OWNER). HE WANTS PERMIT
 TO BE ISSUED WITH PROVISO. JG.