2018-03-29 12:25:03 | NEW SINGLE FAMILY RESIDENCE (R3) SIXTH MECHANICAL |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO |
| ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR |
| IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| |
| 1- IT LOOKS LIKE THE EQUIPMENT MAY BE OVERSIZED AGAIN. |
| IT LOOKS LIKE THE EQUIPMENT WAS SIZED BASED ON A LARGE |
| NUMBER OF PEOPLE. 35 PEOPLE IS A LARGE QUANTITY FOR A |
| SINGLE FAMILY RESIDENCE. EQUIPMENT CAN NOT BE SIZED |
| BASED ON OTHER FACTORS THAT MAY AFFECT THE EQUIPMENT |
| SIZING. REVISE CALCULATIONS AS REQUIRED TO MATCH ACTUAL |
| DESIGN CONDITIONS REQUIRED BY SEC. R403.6.1 FBC-ENERGY |
| CONSERVATION. NOTE: COORDINATE DRAWING M.1 WITH REVISED |
| EQUIPMENT SIZING CALCULATIONS. |
| |
| |
| 2- EQUIPMENT SHOWN ON A/C PLAN DOESN'T MATCH EQUIPMENT |
| SHOWN ON THE AHRI CERTIFICATES SUBMITTED. REVISE AS |
| REQUIRED TO MATCH. NOTE: COORDINATE WITH ITEM #1 ABOVE. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T |
| STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR |
| REFERENCE. |
| |