Plan Review Notes
Plan Review Notes For Permit 16010225
Permit Number 16010225
Review Stop B
Sequence Number 7
Notes
Date Text
2018-03-29 08:34:23NEW SINGLE FAMILY RESIDENCE (R3) SIXTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 IMPORTANT:
 NEED OWNER TO SIGN THE ENERGY CALCULATIONS FOR PROVISO
 OPTION. PERMIT CAN NOT BE ISSUED WITHOUT THE OWNER'S
 CERTIFICATION.
  
  
 1-ENERGY CALCULATIONS SUBMITTED:
 A) THE OWNER OR OWNER'S AUTHORIZED AGENT NEEDS TO
 CERTIFY AND DATE THE ENERGY CALCULATIONS AT THE BOTTOM
 OF FORM AS REQUIRED BY SEC. R103.1.1.2 FBC- ENERGY
 CONSERVATION. THE FORM SUBMITTED ONLY HAVE THE NAME OF
 THE PERSON PREPARING THE ENERGY CALCULATIONS. NEED THE
 OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY
 COMPLIANCE. PERMIT CAN NOT BE ISSUED WITHOUT THE
 OWNER'S CERTIFICATION.
  
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) CONDITIONED FLOOR AREA SHOWN ON ITEM #6 WAS REVISED.
 NOW, IT DOESN'T MATCH FLOOR PLANS. REVISE AS REQUIRED.
 (NOTE: REVISE THE AREAS SHOWN ON ITEM #8 ACCORDINGLY).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 C) ROOF MATERIAL SHOWN ON PAGE 2 OF 5 WAS REVISED. NOW
 IT DOESN'T MATCH MATERIAL SPECIFIED ON PLANS. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 D) THERE ARE TWO NEW INSULATED DOORS SHOWN ON PAGE 3 OF
 5. THERE ARE NOT INSULATED DOORS SPECIFIED ON PLANS OR
 PRODUCT APPROVALS SUBMITTED. WHERE ARE THESE DOORS.
 REVISE AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 E) ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. PREPARER TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE HOUSE COMPLIES WITH THE
 CEILING FAN CREDIT AS REQUIRED BY SEC. R405.7.6 FBC
 ENERGY CONSERVATION. SHOW ALL CEILING FAN SIZES AND
 LOCATION.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 F) ENERGY CALCULATIONS SHOW AN ATTIC VENT RATIO OF
 1/300 ON PAGE 2 OF 5. SEC. R806.2 OF THE
 FBC-RESIDENTIAL REQUIRES 1/150 RATIO. PLANS DON'T SEEM
 TO HAVE THE HOUSE DESIGNED FOR 1/300 VENT RATIO.
 PREPARER TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING HOW THE HOUSE COMPLIES WITH THE 1/300 RATIO AS
 REQUIRED BY EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT
 USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  