2018-03-29 08:34:23 | NEW SINGLE FAMILY RESIDENCE (R3) SIXTH BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO |
| ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR |
| IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| IMPORTANT: |
| NEED OWNER TO SIGN THE ENERGY CALCULATIONS FOR PROVISO |
| OPTION. PERMIT CAN NOT BE ISSUED WITHOUT THE OWNER'S |
| CERTIFICATION. |
| |
| |
| 1-ENERGY CALCULATIONS SUBMITTED: |
| A) THE OWNER OR OWNER'S AUTHORIZED AGENT NEEDS TO |
| CERTIFY AND DATE THE ENERGY CALCULATIONS AT THE BOTTOM |
| OF FORM AS REQUIRED BY SEC. R103.1.1.2 FBC- ENERGY |
| CONSERVATION. THE FORM SUBMITTED ONLY HAVE THE NAME OF |
| THE PERSON PREPARING THE ENERGY CALCULATIONS. NEED THE |
| OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY |
| COMPLIANCE. PERMIT CAN NOT BE ISSUED WITHOUT THE |
| OWNER'S CERTIFICATION. |
| |
| REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| |
| B) CONDITIONED FLOOR AREA SHOWN ON ITEM #6 WAS REVISED. |
| NOW, IT DOESN'T MATCH FLOOR PLANS. REVISE AS REQUIRED. |
| (NOTE: REVISE THE AREAS SHOWN ON ITEM #8 ACCORDINGLY). |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| |
| C) ROOF MATERIAL SHOWN ON PAGE 2 OF 5 WAS REVISED. NOW |
| IT DOESN'T MATCH MATERIAL SPECIFIED ON PLANS. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| |
| D) THERE ARE TWO NEW INSULATED DOORS SHOWN ON PAGE 3 OF |
| 5. THERE ARE NOT INSULATED DOORS SPECIFIED ON PLANS OR |
| PRODUCT APPROVALS SUBMITTED. WHERE ARE THESE DOORS. |
| REVISE AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| |
| E) ENERGY CALCULATIONS ARE TAKING THE CEILING FAN |
| CREDIT. PREPARER TO PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING HOW THE HOUSE COMPLIES WITH THE |
| CEILING FAN CREDIT AS REQUIRED BY SEC. R405.7.6 FBC |
| ENERGY CONSERVATION. SHOW ALL CEILING FAN SIZES AND |
| LOCATION. |
| REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| |
| F) ENERGY CALCULATIONS SHOW AN ATTIC VENT RATIO OF |
| 1/300 ON PAGE 2 OF 5. SEC. R806.2 OF THE |
| FBC-RESIDENTIAL REQUIRES 1/150 RATIO. PLANS DON'T SEEM |
| TO HAVE THE HOUSE DESIGNED FOR 1/300 VENT RATIO. |
| PREPARER TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| SHOWING HOW THE HOUSE COMPLIES WITH THE 1/300 RATIO AS |
| REQUIRED BY EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL. |
| REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| |
| NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR |
| AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS |
| WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT |
| USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T |
| STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR |
| REFERENCE. |
| |