2016-09-28 16:48:13 | NEW SINGLE FAMILY RESIDENCE (R3) FIFTH MECHANICAL | | REVIEW CHECKLIST. | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- IT LOOKS LIKE THE EQUIPMENT MAY BE OVERSIZED AGAIN. | | IT LOOKS LIKE THE EQUIPMENT WAS SIZED BASED ON A LARGE | | NUMBER OF PEOPLE. 35 PEOPLE IS A LARGE QUANTITY FOR A | | SINGLE FAMILY RESIDENCE. EQUIPMENT CAN NOT BE SIZED | | BASED ON OTHER FACTORS THAT MAY AFFECT THE EQUIPMENT | | SIZING. REVISE CALCULATIONS AS REQUIRED TO MATCH ACTUAL | | DESIGN CONDITIONS REQUIRED BY SEC. R403.6.1 FBC-ENERGY | | CONSERVATION. NOTE: COORDINATE DRAWING M.1 WITH REVISED | | EQUIPMENT SIZING CALCULATIONS. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T | | STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR | | REFERENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|