2016-09-28 16:48:13NEW SINGLE FAMILY RESIDENCE (R3) FIFTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- IT LOOKS LIKE THE EQUIPMENT MAY BE OVERSIZED AGAIN.
 IT LOOKS LIKE THE EQUIPMENT WAS SIZED BASED ON A LARGE
 NUMBER OF PEOPLE. 35 PEOPLE IS A LARGE QUANTITY FOR A
 SINGLE FAMILY RESIDENCE. EQUIPMENT CAN NOT BE SIZED
 BASED ON OTHER FACTORS THAT MAY AFFECT THE EQUIPMENT
 SIZING. REVISE CALCULATIONS AS REQUIRED TO MATCH ACTUAL
 DESIGN CONDITIONS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION. NOTE: COORDINATE DRAWING M.1 WITH REVISED
 EQUIPMENT SIZING CALCULATIONS.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  