Plan Review Notes
Plan Review Notes For Permit 16010225
Permit Number 16010225
Review Stop M
Sequence Number 4
Notes
Date Text
2016-08-17 18:26:32NEW SINGLE FAMILY RESIDENCE (R3) FOURTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 ***NOTE:
 MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT PERMIT MAY BE ISSUED AND THE REQUIRED
 INFORMATION MAY BE SUBMITTED AFTER THE PERMIT IS
 ISSUED. REVISION FEES APPLY. REQUIRED INFORMATION TO BE
 SUBMITTED PRIOR TO INSPECTIONS TO AVOID CONFLICTS OR
 DELAYS. CONTRACTOR TO ADVICE IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME.
  
  
  
  
 ORIGINAL COMMENT:
 1- THE EQUIPMENT SIZE FOR UNITS 1 AND 2 IS OVERSIZED.
 ACCORDING TO SEC. R403.6.1.1 FBC-ENERGY CONSERVATION,
 THE EQUIPMENT CAN NOT BE MORE THAN 1.15 TIMES GREATER
 THAN THE TOTAL CALCULATED LOAD OR CLOSEST AVAILABLE
 SIZE. TOTAL COOLING LOADS ARE 27531 BTU'S AND 27192
 BTU'S. THE CLOSES SIZE IS 2-1/2 TON NOT 3 TON. REVISE
 AS REQUIRED INCLUDING SHEET M.1.
  
 RESPONSE:
 REPEAT COMMENT. TOTAL COOLING LOADS SUBMITTED NOW ARE
 26144 BTU'S AND 26736 BTU'S. THE CLOSES SIZE IS 2-1/2
 TON NOT 3 TON. REVISE AS REQUIRED INCLUDING SHEET M.1.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  