2016-08-17 18:26:32 | NEW SINGLE FAMILY RESIDENCE (R3) FOURTH MECHANICAL |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| |
| ***NOTE: |
| MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS THAT PERMIT MAY BE ISSUED AND THE REQUIRED |
| INFORMATION MAY BE SUBMITTED AFTER THE PERMIT IS |
| ISSUED. REVISION FEES APPLY. REQUIRED INFORMATION TO BE |
| SUBMITTED PRIOR TO INSPECTIONS TO AVOID CONFLICTS OR |
| DELAYS. CONTRACTOR TO ADVICE IN WRITING IF PROVISO |
| OPTION IS PREFERRED AT THIS TIME. |
| |
| |
| |
| |
| ORIGINAL COMMENT: |
| 1- THE EQUIPMENT SIZE FOR UNITS 1 AND 2 IS OVERSIZED. |
| ACCORDING TO SEC. R403.6.1.1 FBC-ENERGY CONSERVATION, |
| THE EQUIPMENT CAN NOT BE MORE THAN 1.15 TIMES GREATER |
| THAN THE TOTAL CALCULATED LOAD OR CLOSEST AVAILABLE |
| SIZE. TOTAL COOLING LOADS ARE 27531 BTU'S AND 27192 |
| BTU'S. THE CLOSES SIZE IS 2-1/2 TON NOT 3 TON. REVISE |
| AS REQUIRED INCLUDING SHEET M.1. |
| |
| RESPONSE: |
| REPEAT COMMENT. TOTAL COOLING LOADS SUBMITTED NOW ARE |
| 26144 BTU'S AND 26736 BTU'S. THE CLOSES SIZE IS 2-1/2 |
| TON NOT 3 TON. REVISE AS REQUIRED INCLUDING SHEET M.1. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T |
| STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR |
| REFERENCE. |
| |