Plan Review Notes
Plan Review Notes For Permit 16010225
Permit Number 16010225
Review Stop P
Sequence Number 3
Notes
Date Text
2016-06-16 11:58:211) THE PLANS SHOW A 50 GALLON TANK TYPE WATER HEATER
 AND THE ENERGY CALCULATIONS CALL OUT A 70 GALLON WATER
 HEATER. A TANKLESS WATER HEATER IS ALSO SHOWN IN THE
 GARAGE. CLARIFY.
 2) THE WATER HEATER SHALL MEET THE MINIMUM EFFICIENCIES
 OF TABLE C404.2 IN CHAPT. 4 OF THE FBC, ENERGY
 CONSERVATION FOR THE TYPE OF EQUIPMENT INSTALLED.
 SUBMIT THE CORRECT EF RATING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  