2016-06-15 13:43:38 | NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY |
| SEC. R401.4 OF FBC RESIDENTIAL, 5TH EDITION (2014). |
| |
| RESPONSE: REPEAT COMMENT. 3 TIMES. STILL NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| R401.3 OF FBC RESIDENTIAL, 5TH EDITION (2014). |
| |
| RESPONSE: REPEAT COMMENT. 3 TIMES. STILL NOT ADDRESSED. |
| |
| 3- ENERGY CALCULATIONS SUBMITTED: |
| A) WINDOWS INFORMATION, WHICH INCLUDES DOORS WITH |
| GLAZING, DOESN'T MATCH PLANS. IT LOOKS LIKE THERE ARE |
| MORE WINDOWS SHOWN ON THE ENERGY CALCULATIONS THAN |
| THERE ARE ON PLANS. PLEASE NUMBER EACH WINDOW/DOOR ON |
| THE EXTERIOR ELEVATIONS TO VERIFY THAT INFORMATION |
| MATCHES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| ORIGINAL COMMENT: |
| B) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.3 OF FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| RESPONSE: NOT DONE. REPEAT COMMENT.. 3 TIMES. |
| |
| C) PROVIDE COMPLETE INFORMATION ON TOP OF THE FORM |
| INCLUDING: BUILDER NAME AND PERMIT OFFICE. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| D) THE OWNER OR OWNER'S AUTHORIZED AGENT NEEDS TO |
| CERTIFY AND DATE THE ENERGY CALCULATIONS AT THE BOTTOM |
| OF FORM AS REQUIRED BY SEC. R103.1.1.2 FBC- ENERGY |
| CONSERVATION. ENERGY CALCULATIONS SUBMITTED SHOW THE |
| NAME OF THE OWNER ONLY. THIS IS NOT CERTIFICATION THAT |
| THE OWNER IS COMPLYING WITH THE ENERGY CODE. HE/SHE MAY |
| NOT BE EVEN AWARE OF THIS CERTIFICATION. NEED THE OWNER |
| OR AGENT TO SPECIFICALLY CERTIFY COMPLIANCE. |
| |
| NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR |
| AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS |
| WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT |
| USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| |
| NEW COMMENT: |
| 4- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN AND |
| CROSS VENTILATION CREDITS ON ITEM #15 OF PAGE 1 OF 5. |
| DESIGNER OF RECORD TO PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS ON THE CONSTRUCTION DRAWINGS SHOWING |
| FULL COMPLIANCE WITH SEC. R405.7.6 AND SEC. R405.7.4 OF |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| NOTE: SEE COMMENT REGARDING THE ENERGY CALCULATIONS. |
| MAY BE THAT'S WHY THE CREDITS WERE TAKEN. IT SEEMS THAT |
| THE ENERGY CALCULATIONS ARE SHOWING MORE GLASS THAN |
| THERE IS IN THE HOUSE. |
| |
| ORIGINAL COMMENT: |
| 5- SUBMITTAL PACKAGE IS MISSING ONE SET OF PRODUCT |
| APPROVALS. PROVIDE THE SECOND SET. |
| |
| RESPONSE: THERE ARE SOME PRODUCT APPROVALS THAT ARE |
| MISSING. REVIEW COMPLETE PACKAGE SUBMITTED AND PROVIDE |
| TWO COMPLETE SETS OF PRODUCT APPROVALS REVIEWED BY THE |
| ENGINEER OF RECORD. |
| |
| 6- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T |
| STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR |
| REFERENCE. |
| |