2016-02-18 13:47:45NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED:
 ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE HIS
 NAME AND ALL HIS INFORMATION AND TO PROVIDE ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST.
  
 2- MECHANICAL PLAN M.1 SUBMITTED;
 A) SIZE OF "TRANSFER DUCTS" SHOWN ON THE SECOND FLOOR
 BEDROOMS DON'T COMPLY WITH THE BALANCED RETURN AIR SEC.
 M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014). SHOW
 COMPLIANCE.
  
 B) CLARIFY HOW THE RETURN AREA GRILLS SHOWN ON THE
 FIRST FLOOR BY THE DINING AREA AND ON THE SECOND FLOOR
 BY THE ATTIC ACCESS ARE CONNECTED TO THE AIR HANDLER
 UNIT. SEC. 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  