2016-02-11 07:54:02 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1. PLEASE NOTE THAT THE RISER DIAGRAM SHOWN AT 250A |
| WITH COMBINATION BREAKERS IS NOT TYPICAL AS TO DESIGN |
| OR PRODUCT MANUFACTURING. REVISE RISER DIAGRAM TO SHOW |
| ACTUAL FIELD INSTALLATION FOR THE LOAD CALCULATION |
| SHOWN. FOR EXAMPLE A TYPICAL INSTALLATION WOULD BE A |
| 320A/400A CONTINUOUS METER CAN WITH MAIN BREAKERS SHOWN |
| WIRED FROM METER CAN OR A 400AMP METER COMBO WITH TWO |
| MAINS BREAKERS, FBC 107 MINIMUM PLAN REVIEW CRITERIA. |
| 2. NOTE THAT THE CONDUCTORS SELECTED (3/0) FOR THE |
| 100AMP PANEL IS ABOVE THE STANDARD CAPACITY OF THE |
| TERMINATION LUGS MANUFACTURED FOR 100A PANEL BOARDS. |
| TYPICALLY THESE PANELS HAVE LUGS TO HOLD FROM #6- TO |
| #1/0 MAX. CONDUCTORS. EITHER SHOW SIZED WITH #3 |
| CONDUCTORS FOR 100AMPS OR INCREASE PANEL MAIN BREAKER |
| AND PANEL BOARD ACCORDINGLY. NEC 110.3 FBC 107 |
| 3. SHOW THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR |
| AT THE SERVICE. PER NEC 250.66 |
| 4. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE. |
| A NOTE WILL SUFFICE. NEC 250.94 |
| 5. SHOW CORRECT SIZE OF MCB ON PANEL SCHEDULE A AT 200A |
| NOT 250A. FBC 107 |
| 6. IDENTIFY THE AREAS LABELED AS RECESSED LIGHTING ON |
| PANEL SCHEDULES TO INDICATE SPECIFICALLY THE AREAS |
| SERVED. NEC 408.4 |
| 7. SHOW COMBINATION SMOKE/CO AT BOTH LANDINGS OF THE |
| STAIRS AREA. FBC RES 314 |
| 8. IF THE COUNTERTOP SPACE TO THE LEFT OF RANGE SHOWN |
| IS 12? OR MORE PLEASE SHOW A RECEPTACLE FOR THAT AREA |
| PER NEC 210.52C1. LABEL GFCI |
| 9. PROVIDE A GENERAL NOTE TO PLANS TO INDICATE THE |
| REQUIREMENTS FBC EC 405.1- NO LESS THAN 75% OF LAMPS TO |
| BE HIGH EFFICACY LAMPS. |
| 10. SHOW LOCATION OF THE ELECTRICAL SERVICE ON THE |
| FLOOR PLAN. FBC 107 |
| 11. FURTHER COMMENTS MAY FOLLOW PENDING COMMENTS BEING |
| ADDRESSED. |
| |