Plan Review Notes
Plan Review Notes For Permit 16010207
Permit Number 16010207
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-01-26 11:58:54PERMIT #16010207
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SEE BUILDING PLAN REVIEWER COMMENTS.
  
 2) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 3) PLANS DO NOT INDICATE WHETHER THE BUILDING/SUITES
 HAVE A FIRE ALARM SYSTEM AND/OR A FIRE SPRINKLER
 SYSTEM.
  