2016-01-12 11:01:481ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010199
 1/12/16
  
 1) THE REFECTIVE CEILING PLAN INDICATES RELOCATIONS OF
 AC DIFFUSERS AT THE NEW WINE BARREL CEILING. PLEASE
 SHOW THESE RELOCATIONS AND DETAILS ON SHEET M1.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 GAS-FIRED WATER HEATER AND COOKING APPLIANCES. PLEASE
 NOTE THE GWH DETAIL ON SHEET P-3 DOES NOT APPEAR TO
 MATCH THE TYPE OF UNIT SHOWN ON M-1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  