2016-01-19 08:32:42 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16010199 |
| ADD: 651 OKEECHOBEE BLVD. SUITE # 150 |
| CONT: CHANDLIER CONSTRUCTION |
| TEL: 561-791-6934 |
| E-MAIL: |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JAN. 19/ 2016 |
| ACTION: DENIED |
| |
| 1) SHEET A0.0 UNDER THE HEDING OF BUILDING NFORMATION |
| LIST THIS AS A 14 STORY BUILDING, TYPE IB. PLEASE NOTE |
| FOR EITHER A BUSINESS OR R2 OCCUPANCY THE BUILDING TYPE |
| WOULD BE A TYPE 1A NOT A 1B. SEE 2014 FBC-B TABLE 503. |
| |
| 2) SHEET A-1.0 INDICATES THERE ARE 278 OCCUPANTS WHERE |
| DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF |
| FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES |
| AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| WITH 902. THE PLANS INDICATE WHERE 13 ACCESSIBLE |
| OCCUPANT LOCATIONS ON THE PLANS. THE 2014 |
| FBC-ACCESSIBILITY CODE SECTION 226.1 REQUIRING 5 |
| PERCENT OF 278 OCCUPANTS (278 X 0.5%= 13.9) OR 14 |
| ACCESSIBLE SPACES. |
| |
| 3) SHEET A-1.0 INDICATES (2) BARS THE TOTAL OCCUPANT |
| LOAD OF BOTH BARS IS 26. 26 X 0.5%= 1.3 OR 2 ACCESSIBLE |
| SPACES SHOULD BE OFFERED AT THE BARS, THEY SHOULD BE |
| DISPERSED. 2014 FBC-ACCESSIBILITY CODE 226.2 |
| DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED |
| TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE |
| SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK |
| SURFACES. |
| |
| 4) NONE OF THE PLANS SHOW COMPLIANCE WITH THE 2014 |
| FBC-ACCESSIBILITY CODE FOR 902.3 HEIGHT. THE TOPS OF |
| DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES |
| (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE |
| THE FINISH FLOOR OR GROUND. |
| |
| 5) SHEET A5.1 PLEASE PROVIDE THE CALCULATIONS FOR THE |
| WEIGHT OF THE DROPPED WINE BARREL CEILING, AND PROVIDE |
| CALCULATIONS FOR THE FASTENERS ULTAMATE LOADS THEY CAN |
| HOLD ALLOWABLE LOADS FOR TAP CONS THAT WERE NOT |
| INSPECTED AND THE DERATING TO BE TAKEN, LIST THE TYPE |
| OF FASTENER, & MANUFACTURER. |
| |
| 6) SHEET A5.1 THE DROPPED WINE BARREL CEILING, PLEASE |
| PROVIDE COMPLIANCE WITH THE 2014 FBC-B SECTION 803.11.2 |
| SET-OUT CONSTRUCTION. |
| WHERE WALLS AND CEILINGS ARE REQUIRED TO BE OF |
| FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION |
| AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES |
| GREATER THAN SPECIFIED IN SECTION 803.11.1, CLASS A |
| FINISH MATERIALS, IN ACCORDANCE WITH SECTION 803.1.1 OR |
| 803.1.2, SHALL BE USED. |
| EXCEPTIONS: |
| 1. WHERE INTERIOR FINISH MATERIALS ARE PROTECTED ON |
| BOTH SIDES BY AN AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |