2016-01-19 08:32:42BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010199
 ADD: 651 OKEECHOBEE BLVD. SUITE # 150
 CONT: CHANDLIER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 19/ 2016
 ACTION: DENIED
  
 1) SHEET A0.0 UNDER THE HEDING OF BUILDING NFORMATION
 LIST THIS AS A 14 STORY BUILDING, TYPE IB. PLEASE NOTE
 FOR EITHER A BUSINESS OR R2 OCCUPANCY THE BUILDING TYPE
 WOULD BE A TYPE 1A NOT A 1B. SEE 2014 FBC-B TABLE 503.
  
 2) SHEET A-1.0 INDICATES THERE ARE 278 OCCUPANTS WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. THE PLANS INDICATE WHERE 13 ACCESSIBLE
 OCCUPANT LOCATIONS ON THE PLANS. THE 2014
 FBC-ACCESSIBILITY CODE SECTION 226.1 REQUIRING 5
 PERCENT OF 278 OCCUPANTS (278 X 0.5%= 13.9) OR 14
 ACCESSIBLE SPACES.
  
 3) SHEET A-1.0 INDICATES (2) BARS THE TOTAL OCCUPANT
 LOAD OF BOTH BARS IS 26. 26 X 0.5%= 1.3 OR 2 ACCESSIBLE
 SPACES SHOULD BE OFFERED AT THE BARS, THEY SHOULD BE
 DISPERSED. 2014 FBC-ACCESSIBILITY CODE 226.2
 DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED
 TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE
 SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK
 SURFACES.
  
 4) NONE OF THE PLANS SHOW COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE FOR 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 5) SHEET A5.1 PLEASE PROVIDE THE CALCULATIONS FOR THE
 WEIGHT OF THE DROPPED WINE BARREL CEILING, AND PROVIDE
 CALCULATIONS FOR THE FASTENERS ULTAMATE LOADS THEY CAN
 HOLD ALLOWABLE LOADS FOR TAP CONS THAT WERE NOT
 INSPECTED AND THE DERATING TO BE TAKEN, LIST THE TYPE
 OF FASTENER, & MANUFACTURER.
  
 6) SHEET A5.1 THE DROPPED WINE BARREL CEILING, PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B SECTION 803.11.2
 SET-OUT CONSTRUCTION.
 WHERE WALLS AND CEILINGS ARE REQUIRED TO BE OF
 FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION
 AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES
 GREATER THAN SPECIFIED IN SECTION 803.11.1, CLASS A
 FINISH MATERIALS, IN ACCORDANCE WITH SECTION 803.1.1 OR
 803.1.2, SHALL BE USED.
 EXCEPTIONS:
 1. WHERE INTERIOR FINISH MATERIALS ARE PROTECTED ON
 BOTH SIDES BY AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  