2018-06-25 09:55:391ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16010117
 6/25/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE FIFTH EDITION 2014
 FBC M- FLORIDA MECHANICAL CODE FIFTH EDITION 2014
 FBC EC- FLORIDA ENERGY CONSERVATION CODE FIFTH EDITION
 2014
 FBC EX- FLORIDA EXISTING BUILDING CODE FIFTH EDITION
 2014
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE VALUE OF THE PROJECT HAS INCREASED DUE TO THE
 ADDITION OF TWO NEW 5-TON RTU'S, AND THE MODIFIED AIR
 DISTRIBUTION SYSTEMS. THE ORIGINAL APPROVED PLANS WERE
 FOR ONE 3-TON SYSTEM AND ONE DUCT TRUNK LINE. THE
 ADJUSTED VALUE SHALL INCLUDE THE MECHANICAL LABOR,
 MATERIALS, EQUIPMENT, AND THE STRUCTURAL AND ELECTRICAL
 WORK REQUIRED FOR INSTALLATION OF THE NEW SYSTEMS.
  
 2) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF RTU'S PER SECTION 606.2.1 FBC M. PLEASE NOTE
 THAT THE PLANS ARE UNDER THE FBC M FIFTH EDITION 2014.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER