Plan Review Notes
Plan Review Notes For Permit 16010117
Permit Number 16010117
Review Stop FIRE
Sequence Number 6
Notes
Date Text
2018-06-15 12:36:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1.1 - THE DOUBLE WALL SEPARATING THE
 EXISTING OCCUPANY DOES NOT INDICATE A FIRE RATING OR
 LISTING. IS IT THE INTENT TO HAVE THIS WALL NONRATED?
  
 PER NFPA 101, CHAPTER 6
  
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE JUSTIFICATION WITH
 SPECIFIC CODE REFERENCES.
  
  
 2) SHEET A 1.1 - TWO SETS OF DOUBLE DOORS ARE INDICATED
 ON THE OTHER EXISTING OCCUPANCY THAT DOES NOT INDICATE
 A FIRE RATING. IS IT THE INTENT TO CONNECT THESE SPACES
 AS ONE OCCUPANCY? IS IT THE INTENT TO SEPARATED THESE
 TWO SPACES AT SOME TIME IN THE FUTURE? IF FUTURE
 SEPARATION IS INTEND, THIS WALL SHOULD CARRY A FIRE
 RATING.
  
 PLEASE REVIEW AND ADDRESS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  