Plan Review Notes
Plan Review Notes For Permit 16010117
Permit Number 16010117
Review Stop P
Sequence Number 5
Notes
Date Text
2018-06-28 18:38:411ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE REAR GRAB BAR SHALL COMPLY WITH FBC ACC 604.5.2
 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36 INCHES
 LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
  
 2. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE IF MEASURED AT 36" TO THE CENTER OF
 THE BAR IT CREATES A CODE VIOLATION. PER FBC ACC 609.4
  
 3. ON THE ORIGINAL PLAN THAT I APPROVED HAD NEW ROOF
 DRAINS PLEASE PROVIDE STORM WATER ISOMETRIC DRAWING
 WITH SIZING CALCULATIONS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  