2017-04-14 16:19:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010117
 ADD: 431 BUNKER RD.
 CONT: TBD
 TEL: 561-603-0434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 3RD REVIEW
 DATE: FRI. APRIL 14/ 2017
 ACTION: DENIED
  
 1A) 3ND REQUEST. THE SUBMITTED PAPERWORK IS FOR TAX
 PURPOSES ONLY, IT IS NOT A UNITY OF TITLE, IT HAS BEEN
 REVIEWED BY BOTH MANUEL GONZALEZ AND VINCENT J NOEL.
 1B) COMPLIED. THE PERMIT APPLICATION INDICATES WORK
 UNDER THIS PERMIT WILL BE LOCATED AT 431 BUNKER BY THE
 PCN 73-43-44-04-05-000-0110. SHEET A-100 IT APPEARS
 THIS INFILL OF A BUILDING IS ACTUALLY LOCATED ON THE
 LOT JUST EAST OF THE PROPERTY LOCATED AT 431 BUNKER, AT
 417 BUNKER RD, PCN 74-43-44-04-05-000-0070. DISCREPANCY
 IN INFORMATION. ADDITIONAL INFORMATION
 REQUIRED.107.2.1.3.
  
 2) COMPLIED. THE COVERSHEET, A-000 INDICATES THE PLANS
 UNDER THE HEADING APPLICABLE CODES IS DESIGNED TO THE
 2014 FBC-B BUT UNDER THE GENERAL NOTES THE PLANS
 INDICATE THE DESIGN IS UNDER THE 2007 FBC EDITION.
 PLEASE UPDATE ALL REFERENCES TO THE 2007 FBC. THE 2014
 FBC OR THE 5TH EDITION OF THE FLORIDA BUILDING CODE WAS
 ADOPTED STATEWIDE ON JUNE 30/2015.
  
 3A) 3RD REQUEST.431 BUNKER RD. THE COVERSHEET, A-000
 INDICATES WITH THE PROPOSED 1,680 SQ. FT. ADDITION TO
 AN EXISTING 7909 SQ. FOOTAGE EXISTING BUILDING TOTALING
 9,589 SQ. FT. W/ MEZZANINE INCLUDED. THE ADDITION
 TRANSGRESSES THE PROPERTY LINE AND THAT WILL REQUIRE
 THE UNITY OF TITLE. THE OTHER BUILDING LOCATED AT 417
 BUNKER WILL BECOME A SEPARATE BUILDING WITH A 3 HOUR
 FIRE WALL THAT WILL MEET ALL OF THE FIRE WALL
 REQUIREMENTS. TO BE DISCUSSED LATER ON IN THIS REVIEW.
  
 UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 3B) THE SECOND ISSUE THAT WILL NEED TO BE ADDRESSED IS
 THE 431 BUNKER RD. BUILDING BEING DECLARED BUILDING
 TYPE VB AND A S1 STORAGE OCCUPANCY OF 9,589 SQ. FT.
 NON-SPRINKLERED BUILDING(BUILDING # 1). IN THE 2014
 FBC-B TABLE 503 ALLOWS FOR THIS OCCUPANCY AND BUILDING
 TYPE AN ALLOWABLE 9,000 SQ. FT. PLEASE PROVIDE HOW
 COMPLIANCE WITH TABLE FBC-B 503 AND BUILDING AREA
 MODIFICATIONS FOR THIS BUILDING AS WELL THE BUILDING AT
 417 BUNKER RD. WITH AN AREA OF 9805 SQ. FT. (BUILDING #
 2).
  
 4) NEW COMMENT. SHEET A-201 THERE IS A DISCREPANCY IN
 THE PLANS. THE BUILDING AT 431 BUNKER RD. ON THE
 EXISTING BUILDING SHOW A DOOR THROUGH INTO THE NEW
 ADDITION (PROPOSED PLAN) EAST SIDE OF THE EXISTING
 BUILDING. UNDER THE ISSUED PERMIT 14090842 ON THE EAST
 WALL THERE WAS NO DOOR. PLEASE PROVIDE ADDITIONAL
 INFORMATION ABOUT THIS OPENING. 107.2.1.3.
  
 5) 2ND REQUEST. THE SUBMITTED ROOFING PRODUCT APPROVAL
 REPORT FL 16739-R7 SHEET 4OF 5 PRODUCT DESCRIPTION
 EVERGUARD PVC-60 IS UNDERLINED. APPENDIX1, ON PAGE 1 OF
 34 HAS CIRCLED THE DECK TYPE STEEL DECK. NOTE NONE OF
 THE SUB-SYSTEMS ARE IDENTIFIED IN THE REST OF THE
 APPENDIX AS TO WHICH WILL BE USED IN THE ROOF
 APPLICATION. NOTE IDENTIFY THE SUB-SYSTEM AND NOT THE
 POUNDS PER SQUARE FOOT AND IF THERE IS A ASTERISK OR
 NOT. PAGE 4 OF 5 LIMITATION 5.8 SYSTEMS MARKED WITH A
 ASTERISK ENHANCED FASTENING IS NOT ALLOWED.
 SHEET A-401 INDICATES THE USE OF ROOF TOP INSULATION OF
 R-30/ METAL B DECK.
  
 6) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  