2017-04-14 16:19:50 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16010117 |
| ADD: 431 BUNKER RD. |
| CONT: TBD |
| TEL: 561-603-0434 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| CORRECT A CODE VIOLATION. |
| |
| 3RD REVIEW |
| DATE: FRI. APRIL 14/ 2017 |
| ACTION: DENIED |
| |
| 1A) 3ND REQUEST. THE SUBMITTED PAPERWORK IS FOR TAX |
| PURPOSES ONLY, IT IS NOT A UNITY OF TITLE, IT HAS BEEN |
| REVIEWED BY BOTH MANUEL GONZALEZ AND VINCENT J NOEL. |
| 1B) COMPLIED. THE PERMIT APPLICATION INDICATES WORK |
| UNDER THIS PERMIT WILL BE LOCATED AT 431 BUNKER BY THE |
| PCN 73-43-44-04-05-000-0110. SHEET A-100 IT APPEARS |
| THIS INFILL OF A BUILDING IS ACTUALLY LOCATED ON THE |
| LOT JUST EAST OF THE PROPERTY LOCATED AT 431 BUNKER, AT |
| 417 BUNKER RD, PCN 74-43-44-04-05-000-0070. DISCREPANCY |
| IN INFORMATION. ADDITIONAL INFORMATION |
| REQUIRED.107.2.1.3. |
| |
| 2) COMPLIED. THE COVERSHEET, A-000 INDICATES THE PLANS |
| UNDER THE HEADING APPLICABLE CODES IS DESIGNED TO THE |
| 2014 FBC-B BUT UNDER THE GENERAL NOTES THE PLANS |
| INDICATE THE DESIGN IS UNDER THE 2007 FBC EDITION. |
| PLEASE UPDATE ALL REFERENCES TO THE 2007 FBC. THE 2014 |
| FBC OR THE 5TH EDITION OF THE FLORIDA BUILDING CODE WAS |
| ADOPTED STATEWIDE ON JUNE 30/2015. |
| |
| 3A) 3RD REQUEST.431 BUNKER RD. THE COVERSHEET, A-000 |
| INDICATES WITH THE PROPOSED 1,680 SQ. FT. ADDITION TO |
| AN EXISTING 7909 SQ. FOOTAGE EXISTING BUILDING TOTALING |
| 9,589 SQ. FT. W/ MEZZANINE INCLUDED. THE ADDITION |
| TRANSGRESSES THE PROPERTY LINE AND THAT WILL REQUIRE |
| THE UNITY OF TITLE. THE OTHER BUILDING LOCATED AT 417 |
| BUNKER WILL BECOME A SEPARATE BUILDING WITH A 3 HOUR |
| FIRE WALL THAT WILL MEET ALL OF THE FIRE WALL |
| REQUIREMENTS. TO BE DISCUSSED LATER ON IN THIS REVIEW. |
| |
| UNITY OF TITLE. |
| THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL |
| BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM |
| 'THE SITE'. A 'UNITY OF TITLE' SHALL BE |
| RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE |
| 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT |
| APPLICABLE. |
| SEE WEBSITE FOR APPLICATION: |
| HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| "APPLICATION FOR UNITY OF TITLE" |
| HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| -38-UNITYOFTITLE3.PDF |
| VINCENT J NOEL |
| SURVEYOR/REAL ESTATE SUPERVISOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33401 |
| PHONE: 494-1040 EXT: 1096 |
| FAX: 494-1116 |
| E-MAIL: [email protected] |
| ********************************************* |
| MANUEL JULIAN GONZALEZ |
| ENGINEERING PROJECT COORDINATOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET, 4TH FLOOR |
| WEST PALM BEACH, FL 33401 |
| (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| MAIN PHONE: (561) 822-1200 |
| DIRECT: (561) 494-1085 |
| FAX: (561) 494-1116 |
| MOBILE: (561) 644-7301 |
| EMAIL: [email protected] |
| WWW.WPB.ORG/ENGINEERING |
| |
| 3B) THE SECOND ISSUE THAT WILL NEED TO BE ADDRESSED IS |
| THE 431 BUNKER RD. BUILDING BEING DECLARED BUILDING |
| TYPE VB AND A S1 STORAGE OCCUPANCY OF 9,589 SQ. FT. |
| NON-SPRINKLERED BUILDING(BUILDING # 1). IN THE 2014 |
| FBC-B TABLE 503 ALLOWS FOR THIS OCCUPANCY AND BUILDING |
| TYPE AN ALLOWABLE 9,000 SQ. FT. PLEASE PROVIDE HOW |
| COMPLIANCE WITH TABLE FBC-B 503 AND BUILDING AREA |
| MODIFICATIONS FOR THIS BUILDING AS WELL THE BUILDING AT |
| 417 BUNKER RD. WITH AN AREA OF 9805 SQ. FT. (BUILDING # |
| 2). |
| |
| 4) NEW COMMENT. SHEET A-201 THERE IS A DISCREPANCY IN |
| THE PLANS. THE BUILDING AT 431 BUNKER RD. ON THE |
| EXISTING BUILDING SHOW A DOOR THROUGH INTO THE NEW |
| ADDITION (PROPOSED PLAN) EAST SIDE OF THE EXISTING |
| BUILDING. UNDER THE ISSUED PERMIT 14090842 ON THE EAST |
| WALL THERE WAS NO DOOR. PLEASE PROVIDE ADDITIONAL |
| INFORMATION ABOUT THIS OPENING. 107.2.1.3. |
| |
| 5) 2ND REQUEST. THE SUBMITTED ROOFING PRODUCT APPROVAL |
| REPORT FL 16739-R7 SHEET 4OF 5 PRODUCT DESCRIPTION |
| EVERGUARD PVC-60 IS UNDERLINED. APPENDIX1, ON PAGE 1 OF |
| 34 HAS CIRCLED THE DECK TYPE STEEL DECK. NOTE NONE OF |
| THE SUB-SYSTEMS ARE IDENTIFIED IN THE REST OF THE |
| APPENDIX AS TO WHICH WILL BE USED IN THE ROOF |
| APPLICATION. NOTE IDENTIFY THE SUB-SYSTEM AND NOT THE |
| POUNDS PER SQUARE FOOT AND IF THERE IS A ASTERISK OR |
| NOT. PAGE 4 OF 5 LIMITATION 5.8 SYSTEMS MARKED WITH A |
| ASTERISK ENHANCED FASTENING IS NOT ALLOWED. |
| SHEET A-401 INDICATES THE USE OF ROOF TOP INSULATION OF |
| R-30/ METAL B DECK. |
| |
| 6) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |