Plan Review Notes
Plan Review Notes For Permit 16010117
Permit Number 16010117
Review Stop P
Sequence Number 2
Notes
Date Text
2016-03-27 08:32:011) SUBMIT A STORMWATER RISER FOR THE PRIMARY ROOF
 DRAINAGE AND FOR THE OVERFLOW DRAINS.THE SIZING OF THE
 HORIZONTAL DRAINS SHALL COMPLY WITH 2014 FBC-PLUMBING
 TABLE 1106.3. THE DESIGN SHALL BE BASED ON A 5 INCH
 RAINFALL RATE PER HOUR.SHOW THE SQUARE FOOTAGE DRAINED
 BY EACH DRAIN. 2ND REQUEST.FBC 107.3.5. THIS HAS NOT
 BEEN SUBMITTED NOR HAS A STORM DRAIN RISER BEEN
 SUBMITTED AS PREVIOUSLY REQUESTED. INDICATE THE SLOPE
 OF THE HORIZONTAL STORM DRAIN.
 2) RAINWATER LEADERS SHALL DISCHARGE A MINIMUM OF ONE
 FOOT FROM THE BUILDING EXTERIOR WALL. 2014 FBC SEC.
 1503.7.
 3) CLEANOUTS ARE REQUIRED IN THE STORM DRAINAGE SYSTEM
 PER 2014 FBC-PLUMBING SEC. 1101.8.
 4) SHOW THE TERMINATION / DISCHARGE POINTS OF THE
 PRIMARY AND OVERFLOW ROOF DRAINS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 5) INDICATE ON THE PLANS HOW THE NEW LANDSCAPED AREAS
 WILL BE IRRIGATED. PLEASE NOTE THIS ON THE PLANS AS
 YOUR RESPONSE TO THE COMMENTS USUALLY DOES NOT MAKE IT
 TO THE FIELD, WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  