Plan Review Notes
Plan Review Notes For Permit 16010117
Permit Number 16010117
Review Stop B
Sequence Number 2
Notes
Date Text
2016-03-29 15:25:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010117
 ADD: 431 BUNKER RD.
 CONT: TBD
 TEL: 561-603-0434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 2ND REVIEW
 DATE: TUES. MARCH 29/ 2016
 ACTION: DENIED
  
 1) 2ND REQUEST. THE SUBMITTED PAPERWORK IS FOR TAX
 PURPOSES ONLY, IT IS NOT A UNITY OF TITLE, IT HAS BEEN
 REVIEWED BY BOTH MANUEL GONZALEZ AND VINCENT J NOEL.
 THE PERMIT APPLICATION INDICATES WORK UNDER THIS PERMIT
 WILL BE LOCATED AT 431 BUNKER BY THE PCN
 73-43-44-04-05-000-0110. SHEET A-100 IT APPEARS THIS
 INFILL OF A BUILDING IS ACTUALLY LOCATED ON THE LOT
 JUST EAST OF THE PROPERTY LOCATED AT 431 BUNKER, AT 417
 BUNKER RD, PCN 74-43-44-04-05-000-0070. DISCREPANCY IN
 INFORMATION. ADDITIONAL INFORMATION REQUIRED.107.2.1.3.
  
 2) COMPLIED. THE COVERSHEET, A-000 INDICATES THE PLANS
 UNDER THE HEADING APPLICABLE CODES IS DESIGNED TO THE
 2014 FBC-B BUT UNDER THE GENERAL NOTES THE PLANS
 INDICATE THE DESIGN IS UNDER THE 2007 FBC EDITION.
 PLEASE UPDATE ALL REFERENCES TO THE 2007 FBC. THE 2014
 FBC OR THE 5TH EDITION OF THE FLORIDA BUILDING CODE WAS
 ADOPTED STATEWIDE ON JUNE 30/2015.
  
 3)2ND REQUEST. THE COVERSHEET, A-000 INDICATES WITH THE
 PROPOSED 1,6778 SQ. FT. ADDITION THE TOTAL SQ. FOOTAGE
 OF THE BUILDING IS 19,389 SQ. FT. THE 431 BUNKER RD.
 BUILDING WITH MEZZANINE SQ. FOOTAGE IS 7912 SQ, FT. THE
 417 BUNKER RD. BUILDING FROM THE PROPERTY APPRAISERS
 SITE IS 9780 SQ. FT. PLUS THE NEW PROPOSED ADDITION OF
 1,680 SQ. FT. IS 19,372 SQ. FT. THIS MEANS THE
 BUILDINGS ARE CROSSING OVER PROPERTY LINES AND WILL
 REQUIRE A UNITY OF TITLE. THE OTHER ISSUE SHEET A-202
 SHOWS NEW OPENINGS IN THE PROPERTY LINE WALL.
  
 UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 4) THE COVERSHEET, A-000 INDICATES THE TOTAL SQUARE
 FOOT AREA OF THE COMBINED BUILDINGS TO ENCOMPASS 19,389
 SQUARE FEET. PLEASE SEE THE 2014 FBC-EXISTING BUILDING
 SECTION 1101.2 CREATION OR EXTENSION OF NONCONFORMITY.
 AN ADDITION SHALL NOT CREATE OR EXTEND ANY
 NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH REGARD TO ACCESSIBILITY,
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR
 THE CAPACITY OF MECHANICAL, PLUMBING, OR ELECTRICAL
 SYSTEMS.
  
 4A) 2ND REQUEST. THE PLANS INDICATE THE COMBINED SQ.
 FT. AREA OF THE 2 BUILDINGS ARE OVER 19,000 SQUARE
 FEET. THE AREA LIMITATION OF TABLE 503 IS 9,000 SQ. FT.
 AND ONLY ONE STORY FOR A S1 OCCUPANCY/ NON-SPRINKLERED.
 .
 1ST REVIEW COMMENT. PLEASE PROVIDE WITH THE TOTAL
 COMBINED AREA OF THE 2 BUILDINGS (417 & 431 BUNKER) OF
 19,389 SQ. FT. THE MINIMUM BUILDING TYPE SEE 2014 FBC-B
 503.
 1102.2 AREA LIMITATIONS. NO ADDITION SHALL INCREASE THE
 AREA OF AN EXISTING BUILDING BEYOND THAT PERMITTED
 UNDER THE APPLICABLE PROVISIONS OF CHAPTER 5 OF THE
 FLORIDA BUILDING CODE, BUILDING FOR NEW BUILDINGS
 UNLESS FIRE SEPARATION AS REQUIRED BY THE FLORIDA
 BUILDING CODE, BUILDING IS PROVIDED.
  
 4B) 2ND REQUEST. NON-SPRINKLERED BUILDING TO COMPLY
 WITH:
 PLEASE SEE THE 2014 EXISTING BUILDING CODE SECTION
 1102.3 FIRE PROTECTION SYSTEMS. EXISTING FIRE AREAS
 INCREASED BY THE ADDITION SHALL COMPLY WITH CHAPTER 9
 OF THE FLORIDA BUILDING CODE, BUILDING. NOT ONLY IS
 THERE AN ADDITION BUT A UNITY OF TITLE INCREASING THE
 SIZE OF THE BUILDING TO OVER 19,000 SQUARE FEET.
  
 2014 FBC-B [F] 903.2.9 GROUP S-1. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT ALL
 BUILDINGS CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF
 THE FOLLOWING CONDITIONS EXISTS:
 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEE.
 5. A GROUP S-1 OCCUPANCY USED FOR THE STORAGE OF
 UPHOLSTERED FURNITURE OR MATTRESSES EXCEEDS 2,500
 SQUARE FEET.
  
 5) THE SUBMITTED ROOFING PRODUCT APPROVAL REPORT FL
 16739-R7 SHEET 4OF 5 PRODUCT DESCRIPTION EVERGUARD
 PVC-60 IS UNDERLINED. APPENDIX1, ON PAGE 1 OF 34 HAS
 CIRCLED THE DECK TYPE STEEL DECK. NOTE NONE OF THE
 SUB-SYSTEMS ARE IDENTIFIED IN THE REST OF THE APPENDIX
 AS TO WHICH WILL BE USED IN THE ROOF APPLICATION. NOTE
 IDENTIFY THE SUB-SYSTEM AND NOT THE POUNDS PER SQUARE
 FOOT AND IF THERE IS A ASTERISK OR NOT. PAGE 4 OF 5
 LIMITATION 5.8 SYSTEMS MARKED WITH A ASTERISK ENHANCED
 FASTENING IS NOT ALLOWED.
 SHEET A-401 INDICATES THE USE OF ROOF TOP INSULATION OF
 R-30/ METAL B DECK.
  
 6) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  