Plan Review Notes
Plan Review Notes For Permit 16010117
Permit Number 16010117
Review Stop P
Sequence Number 1
Notes
Date Text
2016-01-09 07:03:081) SUBMIT A STORMWATER RISER FOR THE PRIMARY ROOF
 DRAINAGE AND FOR THE OVERFLOW DRAINS.THE SIZING OF THE
 VERTICAL LEADERS AND HORIZONTAL DRAINS SHALL COMPLY
 WITH 2014 FBC-PLUMBING, TABLES 1106.2.1 & 1106.3
 RESPECTIVELY. THE DESIGN SHALL BE BASED ON A 5 INCH
 RAINFALL RATE PER HOUR.SHOW THE SQUARE FOOTAGE DRAINED
 BY EACH DRAIN. WPB AMEND. TO FBC SEC. 107.2.1.
 2) VERTICAL WALLS - IN SIZING ROOF DRAINS AND STORM
 DRAINAGE PIPING, ONE-HALF OF THE AREA OF ANY VERTICAL
 WALL THAT DIVERTS RAINWATER TO THE ROOF SHALL BE ADDED
 TO THE PROJECTED ROOF AREA FOR INCLUSION IN CALCULATING
 THE REQUIRED SIZE OF VERTICAL CONDUCTORS, LEADERS AND
 HORIZONTAL STORM DRAINAGE PIPING.
 3) CLEANOUTS ARE REQUIRED IN THE STORM DRAINAGE SYSTEM
 PER 2014 FBC-PLUMBING SEC. 1101.8.
 4) SHOW THE TERMINATION / DISCHARGE POINTS OF THE
 PRIMARY AND OVERFLOW ROOF DRAINS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 5) SUPPLY THE NUMBER OF EXISTING SANITARY FACILITIES TO
 ENSURE THAT THEY WILL BE ADEQUATE FOR THE ADDED
 OCCUPANT LOAD.REFER TO 2014 FBC-PLUMBING TABLE 403.1.
 6) INDICATE ON THE PLANS HOW THE NEW LANDSCAPED AREAS
 WILL BE IRRIGATED. WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  