2016-01-15 14:47:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1. SHEET - 201 - ON THE DOOR SCHEDULE UNDER HARDWARE |
| SET THE NUMBER 1 IS PROVIDED. THERE IS NO INDICATION OF |
| WHAT THAT # 1 REPRESENTS. PLEASE PROVIDE THE HARDWARE |
| SET TYPE AND LOCKING MECHANISM THAT COMPLIES WITH NFPA |
| 101, CHAPTER 7, MEANS OF EGRESS. |
| |
| 2. SHEET - 201 - THERE IS NOT INDICATION OF AN EXIT |
| SIGN AT THE NEW INSTALLED DOOR COMPLYING WITH NFPA 101, |
| CHAPTER 7, MEANS OF EGRESS. |
| |
| 3. SHEET - 201 - THERE IS NO INDICATION OF EMERGENCY |
| LIGHTING ALONG THE PATH OF EGRESS COMPLYIING WITH NFPA |
| 101, CHAPTER 7, MEANS OF EGRESS. |
| |
| 4. SHEET 202 - PER FLORIDA 69A-60.0081; NOTICE SIGNAGE |
| IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE |
| CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY |
| MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE |
| WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| MARKED WITH THE LETTER "R". |
| B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| SHALL BE MARKED WITH THE LETTER "F". |
| C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| |