2016-02-02 13:59:53 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| ELECTRICAL REVIEW COMMENTS. |
| |
| PROVIDE AN ELECTRICAL PLAN WITH THE FOLLOWING: |
| ELECTRICAL RISER PLAN SHOWING ALL FEEDERS, DISCONNECTS |
| AND PANEL BOARDS |
| LOCATION OF THE ELECTRICAL SERVICE AND MAIN |
| DISCONNECTS |
| LOCATION OF ALL ELECTRICAL PANELBOARDS |
| SAFE WORKING SPACE AT ELECTRICAL DISCONNECTS AND |
| PANELBOARDS |
| EXIT AND EMERGENCY ILLUMINATION |
| |
| PROVIDE ELECTRIC NOTES ON THE PLAN INDICATING THE |
| FOLLOWING: |
| GENERAL PURPOSE RECEPTACLES INSTALLED IN THE |
| BATHROOMS, KITCHENS, ROOFTOPS, OUTDOORS, WITHIN SIX |
| FEET OF SINKS,AT ELECTRIC DRINKING FOUNTAINS, AND |
| VENDING MACHINES ARE GFCI PROTECTED. |
| ALL DISCONNECTS SHALL BE LEGIBLY MARKED TO INDICATE |
| THEIR PURPOSE. |
| |
| PROVIDE LIGHTING CONTROLS FOR ENERGY CONSERVATION SO |
| THAT THE INTERIOR AND EXTERIOR LIGHTING CONTROLS |
| PROVIDED FUNCTION IN ACCORDANCE WITH THE FLORIDA ENERGY |
| CODE. EXTERIOR AUTOMATIC CONTROLS SHALL BE CAPABLE OF |
| RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS |
| OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. |
| |
| VERIFY THE LIGHTING AND SIGN TIME CLOCKS HAVE BATTERY |
| BACKUP. FBC ENERGY CONSERVATION 505.2 |
| |
| PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN |
| WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; |
| 505.5.3; T. 505.5.3 |
| |
| CODE REFERENCES: |
| FBC EXISTING BUILDING 908.2, 908.3, 908.4 |
| NEC 110.22, 110.26, 210. 8, 215.5, 422.51, 422.52 |
| |
| ROBERT LECKY |
| ELECTRICAL PLANS EXAMINER |
| |
| |
| |
| |