Notes |
Date |
Text |
2016-02-02 10:46:33 | PLEASE RESPOND TO COMMENTS IN WRITING: | | | | HOW WILL 5" DROP OFF BEHIND 2 STORY BUILDING DRAIN? | | | | RETAINING WALL WILL AFFECT DRAINAGE ON ADJACENT | | PROPERTIES? | | | | SUBMIT TOPOGRAPHIC ELEVATIONS. EXISTING SPOT GRADES ARE | | ILLEGIBLE ON PLAN SHEET. | | NEED TO DETERMINE HOW GRADES CHANGE PATTERNS. | | | | MR. TRACY WARD, SENIOR STORMWATER ENGINEER | | PUBLIC WORKS/ ENGINEERING SERVICES | | 401 CLEMATIS STREET | | P.O.BOX 3366 | | WEST PALM BEACH, FL 33402 | | PHONE: 494-1040 EXT: 1120 | | FAX: 494-1116 | | E-MAIL: [email protected] | | | | ****************************************** | | MANUEL JULIAN GONZALEZ | | ENGINEERING PROJECT COORDINATOR | | PUBLIC WORKS DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | | | IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF | | WEST PALM BEACH | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | FREE." | | FOR MORE INFORMATION REFER TO THE LINK BELOW: | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | | | | | | | | | | | | | |
|