Plan Review Notes For Permit 15120919 |
Permit Number |
15120919 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-29 15:30:01 | NEW SINGLE FAMILY RESIDENCE (R3), MECHANICAL REVIEW | | COMMENTS. | | CODE: FBC 5TH EDITION (2014) | | | | NOTE: | | MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. | | REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF | | PROVISO OPTION IS ACCEPTABLE. | | | | 1- EQUIPMENT SIZING CALCULATIONS NEED TO BE DONE WITH | | THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED BY | | SEC. R403.06 OF FBC-ENERGY CONSERVATION, 5TH EDITION | | (2014). CALCULATIONS SUBMITTED ARE NOT DONE FOR THE | | ACTUAL ORIENTATION OF THE BUILDING. FOR EXAMPLE, THERE | | ARE NOT WINDOWS ON THE WEST SIDE WITH AN OVERHANG | | LENGTH OF 6.5FT. REVISE ALL CALCULATIONS AS REQUIRED TO | | MATCH PLANS. | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] | | | | |
|