Plan Review Notes
Plan Review Notes For Permit 15120919
Permit Number 15120919
Review Stop B
Sequence Number 1
Notes
Date Text
2016-01-28 18:35:48NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. REVISION
 FEES MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS ACCEPTABLE.
  
 1- ENERGY CALCULATIONS SUBMITTED ARE TAKING THE CROSS
 VENTILATION CREDIT. PROVIDE COMPLETE INFORMATION
 SHOWING HOW THE PLANS COMPLY WITH ALL THE REQUIREMENTS
 OF SEC. R405.7.4 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) ITEM #5 OF ENERGY CALCULATIONS STATE THAT THE
 CALCULATIONS ARE NO WORST CASE SCENARIO, BUT PAGE 2 OF
 4 STATES THAT HOUSE WAS ROTATED 90 DEGREES. THIS IS NOT
 CLEAR. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
 NOTE: ENERGY CALCULATIONS MAY BE DONE FOR WORST CASE
 SCENARIO, BUT EQUIPMENT SIZING CALCULATIONS NEED TO BE
 DONE TO THE ACTUAL ORIENTATION OF THE BUILDING.
  
 B) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS
 REQUIRED BY SEC. R103.1.1.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 C) REVISE THE CLIMATE ZONE SHOWN ON PAGE 2 OF 4. SEE
 TABLE C301.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 D) REVISE THE TYPE OF ROOF SHOWN ON PAGE 2 OF 4. PLANS
 SUBMITTED DON'T SHOW HIP ROOF. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.1.1.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 F) COMPLETE THE CHECK LIST ON TABLE 402.4.1.1
 SUBMITTED.
  
 G) COMPLETE THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY
 CARD SUBMITTED.
  
 NOTE:
 LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 3- WINDOW AND DOOR SCHEDULE ON SHEET A-3.0: ENTRY DOOR
 SAYS "NR". CLARIFY WHY THE ENTRY DOOR DOESN'T HAVE TO
 COMPLY WITH THE EGRESS REQUIREMENTS. SEC. R11 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION WAS UPDATED TO $150,000. THE PERMIT FEE
 BALANCE IS $973.38. SEC. 109.3 CITY AMENDMENTS.
  
 5- REVISE THE DESIGN PARAMETERS NOTE ON SHEET A-3.0:
 THE BUILDING DOESN'T HAVE A HIP ROOF. THE DESIGN
 PRESSURES ON A HIP ROOF AND A GABLE ROOF ARE DIFFERENT.
 REVISE AS REQUIRED. SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 6- SIZE OF FOOTING S1 SHOWN ON SHEET S-1.0 DOESN'T
 MATCH SIZE SHOWN ON TYPICAL WALL SECTION.
 REVISE/CLARIFY AS REQUIRED. WHICH ONE IS THE CORRECT
 SIZE?. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 7- RE-SUBMIT PRODUCT APPROVAL REQUIRED BY FAC
 61G20-3.002(33) FOR: EXTERIOR DOORS. FLORIDA PRODUCT
 APPROVAL FL11136-R1 SUBMITTED IS FOR THE 2010 CODE
 VERSION. NEED THE CURRENT 2014 CODE VERSION.
 NOTE: REVISE ALL PRODUCT APPROVAL NUMBERS ON SHEET
 A-3.0 AS WELL.
  
 8- DESIGNER OF RECORD TO APPROVED ABOVE PRODUCT
 APPROVALS PRIOR TO SUBMITTAL. SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 9- REVISE SURVEY. BUILDING IS LOCATED IN FLOOD ZONE "B"
 NOT "C". SEC. 107.2.1 CITY AMENDMENTS.
  
 10- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSIGN EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  