Plan Review Notes For Permit 15120911 |
Permit Number |
15120911 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-13 16:28:52 | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | 1. CLEARLY SHOW HOW THE TUB AND SHOWER ARE CONNECTING | | TO UNDERGROUND PIPING PER WPB AMEND TO FBC SEC107.2.1 | | 2. VENT ON WATER CLOSET IN MASTER BATH IS DRAWN AS A | | FLAT DRY VENT WITCH IS NOT ALLOWED UNLESS CONNECTED | | ABOVE CENTERLINE OF HORIZONTAL DRAIN. PER FBC RES. SEC | | P3104.3 THAT VENT IS NOT REQUIRED WC IS VENTED BY LAV. | | 3.BATH 2 VENT FOR LAV NEEDS TO CONNECT BETWEEN THE WC | | AND TUB. | | |
|