Plan Review Notes For Permit 15120910 |
Permit Number |
15120910 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-31 16:56:51 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE SYSTEM THAT WAS MARKED IN THE PRODUCT APPROVAL | | HAS AN UPLIFT OF -45 PSF, WHICH IS NOT ADEQUATE. SUBMIT | | TWO COPIES OF SIGNED AND SEALED ENGINEERING FOR THE | | ENHANCED FASTENING OF THE BASE SHEET. FBC 1504.1 | | | | 2) SUBMIT TWO COPIES OF A FASTENER PULL TEST. FBC | | 1504.3.1 | | | | 3) SUBMIT TWO COPIES OF A MOISTURE SURVEY OF THE | | LIGHTWEIGHT CONCRETE. FBC EXISTING 708.3 |
|