2016-02-20 06:55:38 | 1) SHT.P1 - THE SHEET IS REQUIRED TO BE SEALED BY THE | | DESIGN PROFESSIONAL OF RECORD. FAC RULE 61G1-16.001. | | 2) THE LAB SINKS SHALL BE STACKED & VENTED. 2014 FPC | | SEC.901.2. | | 3) SHOW ON THE PLANS THAT THE HEIGHT OF THE STAFF | | LOUNGE SINK COMPLIES WITH THE FL. ACCESS. CODE SEC. | | 212.2 & 804.( MAX. 34 INCHES HIGH) | | 4) SHOW ON THE PLANS THAT THE DRINKING FOUNTAINS ARE | | ARRANGED FOR A FORWARD APPROACH PER THE 2014 FAC | | SEC.602.2. | | 5) CLEARLY SHOW THE WIDTH OF THE TOILET ROOMS ON THE | | PLANS. THE TOILET ROOMS SHALL BE A MINIMUM WIDTH OF 85 | | INCHES WHEN THE TOILET AND LAVATORY ARE LOCATED ON THE | | SAME WALL. | | 6) THE HIGH SIDE DRINKING FOUNTAIN SHALL COMPLY WITH | | THE 2014 FAC SEC. 307 FOR PROTRUDING OBJECTS. AN | | OPTIONAL SKIRT MAY BE REQUIRED TO KEEP THE LEADING EDGE | | BELOW 27 INCHES.2014 FAC SEC. 307.2. | | 7) THE RESPONSE FROM THE ARCHITECT REFERS TO A SIDE | | APPROACH FOR THE STAFF LOUNGE SINK BUT A FORWARD | | APPROACH IS SHOWN ON THE PLANS. CLARIFY. | | 8) THE VENT FOR THE LAVS SHALL BE MIN. OF 2 INCH. 2014 | | FPC SEC.906.1. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|