Plan Review Notes
Plan Review Notes For Permit 15120875
Permit Number 15120875
Review Stop P
Sequence Number 2
Notes
Date Text
2016-02-20 06:55:381) SHT.P1 - THE SHEET IS REQUIRED TO BE SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD. FAC RULE 61G1-16.001.
 2) THE LAB SINKS SHALL BE STACKED & VENTED. 2014 FPC
 SEC.901.2.
 3) SHOW ON THE PLANS THAT THE HEIGHT OF THE STAFF
 LOUNGE SINK COMPLIES WITH THE FL. ACCESS. CODE SEC.
 212.2 & 804.( MAX. 34 INCHES HIGH)
 4) SHOW ON THE PLANS THAT THE DRINKING FOUNTAINS ARE
 ARRANGED FOR A FORWARD APPROACH PER THE 2014 FAC
 SEC.602.2.
 5) CLEARLY SHOW THE WIDTH OF THE TOILET ROOMS ON THE
 PLANS. THE TOILET ROOMS SHALL BE A MINIMUM WIDTH OF 85
 INCHES WHEN THE TOILET AND LAVATORY ARE LOCATED ON THE
 SAME WALL.
 6) THE HIGH SIDE DRINKING FOUNTAIN SHALL COMPLY WITH
 THE 2014 FAC SEC. 307 FOR PROTRUDING OBJECTS. AN
 OPTIONAL SKIRT MAY BE REQUIRED TO KEEP THE LEADING EDGE
 BELOW 27 INCHES.2014 FAC SEC. 307.2.
 7) THE RESPONSE FROM THE ARCHITECT REFERS TO A SIDE
 APPROACH FOR THE STAFF LOUNGE SINK BUT A FORWARD
 APPROACH IS SHOWN ON THE PLANS. CLARIFY.
 8) THE VENT FOR THE LAVS SHALL BE MIN. OF 2 INCH. 2014
 FPC SEC.906.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  