Plan Review Notes
Plan Review Notes For Permit 15120875
Permit Number 15120875
Review Stop P
Sequence Number 1
Notes
Date Text
2016-01-15 09:17:011ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.PLEASE PROVIDE A LIST OF CHEMICALS BEING USED AT THIS
 FACILITY.
 2. WHAT STATE ARE THE CHEMICALS IN ,SOLID ,LIQUID, OR
 GAS.
 3. HOW THE CHEMICALS ARE BEING STORED AND IN WHAT
 AMOUNTS.
 4. PLEASE PROVIDE MSDS SHEETS FOR ALL THE CHEMICALS
 BEING USED AND STORED.
 PER WPB AMEND TO FBC 107.2.1
 5. HOW WILL USED CHEMICALS BE DISPOSED OF WILL ANY BE
 GOING INTO THE SANITARY SYSTEM, SHALL COMPLY WITH FBC
 PL SEC 803
 6. PLEASE PROVIDE A BREAK DOWN OF COST TO SHOW
 COMPLIANCE TO FBC ACC SEC 202.4.1-202.4.2
 7. PROVIDE WATER RISER DIAGRAM. PER WPB AMEND TO FBC
 SEC 107.3.5.1.3(13)
 8. SHOW ALL PIPE SIZES ON RISER DIAGRAM. PER WPB AMEND
 TO FBC 107.2.1
 9. WASTE ARMS FOR LAV SHALL COMPLY WITH FBC PL TABLE
 909.1
 10. IS SINK IN STAFF LOUNGE EXISTING.
  
  