2015-12-31 09:52:211ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120875
 12/31/15
  
 1) VENTILATION CALCULATIONS ARE REQUIRED WHEN AC
 SYSTEMS ARE ALTERED- SEE SECTION 809.2 FBC-14 EXISTING
 BUILDING AND SHOW COMPLIANCE.
 2) THE PLAN SHOWS THE CORRIDOR RUNNING BETWEEN THE
 STAFF LOUNGE AND THE DIRECTOR/CONFERENCE ROOM BEING
 USED AS A RETURN AIR DUCT- SEE SECTION 601.2 FBC-14
 MECHANICAL AND CORRECT.
 3) THE PLAN INDICATES UNDERSIZED RETURN AIR TRANSFER
 DUCTS FROM ALL OF THE ROOMS- SEE SECTION 601.5 AND
 CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER