Plan Review Notes For Permit 15120875 |
Permit Number |
15120875 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-31 09:52:21 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15120875 | | 12/31/15 | | | | 1) VENTILATION CALCULATIONS ARE REQUIRED WHEN AC | | SYSTEMS ARE ALTERED- SEE SECTION 809.2 FBC-14 EXISTING | | BUILDING AND SHOW COMPLIANCE. | | 2) THE PLAN SHOWS THE CORRIDOR RUNNING BETWEEN THE | | STAFF LOUNGE AND THE DIRECTOR/CONFERENCE ROOM BEING | | USED AS A RETURN AIR DUCT- SEE SECTION 601.2 FBC-14 | | MECHANICAL AND CORRECT. | | 3) THE PLAN INDICATES UNDERSIZED RETURN AIR TRANSFER | | DUCTS FROM ALL OF THE ROOMS- SEE SECTION 601.5 AND | | CORRECT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|