Plan Review Notes For Permit 15120875 |
Permit Number |
15120875 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-06 16:03:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1. PLEASE PROVIDE DOCUMENTATION ON WHAT THE BUSINESS | | PRODUCES/MANUFACTURE'S/ PROCESSES. WHAT TAKES PLACE IN | | THE LAB? | | | | 2. PROVIDE DOCUMENTATION ON THE NITROGEN GENERATOR AND | | WHAT IT IS USED FOR. PROVIDE THE MANUFACTURES SPEC'S | | INCLUDING INSTALLATION RECOMMENDATIONS/PRECAUTIONS. | | | | 3. EXIT DOOR HARDWARE IS NOT PROVIDED. EXIT DOOR | | LOCKING/LATCHING SHALL COMPLY WITH NFPA 101, 5TH | | EDITION, CHAPTER 7. | | | | 4. EXIT SIGNAGE SHALL BE PROVIDED FOR FROM THE LAB | | AREA. | | | | 5. EMERGENCY LIGHTS SHALL BE PROVIDED FOR IN THE LAB | | AREA. | | | | 6. PROVIDE AN EQUIPMENT PLAN FOR THE LAB. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|