Plan Review Notes
Plan Review Notes For Permit 15120875
Permit Number 15120875
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-01-06 16:03:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE DOCUMENTATION ON WHAT THE BUSINESS
 PRODUCES/MANUFACTURE'S/ PROCESSES. WHAT TAKES PLACE IN
 THE LAB?
  
 2. PROVIDE DOCUMENTATION ON THE NITROGEN GENERATOR AND
 WHAT IT IS USED FOR. PROVIDE THE MANUFACTURES SPEC'S
 INCLUDING INSTALLATION RECOMMENDATIONS/PRECAUTIONS.
  
 3. EXIT DOOR HARDWARE IS NOT PROVIDED. EXIT DOOR
 LOCKING/LATCHING SHALL COMPLY WITH NFPA 101, 5TH
 EDITION, CHAPTER 7.
  
 4. EXIT SIGNAGE SHALL BE PROVIDED FOR FROM THE LAB
 AREA.
  
 5. EMERGENCY LIGHTS SHALL BE PROVIDED FOR IN THE LAB
 AREA.
  
 6. PROVIDE AN EQUIPMENT PLAN FOR THE LAB.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  