2016-02-10 13:28:02INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY WHAT TYPE OF HEALTH FACILITY THIS IS.
 LAB TYPE. FBC 107
 2. PROVIDE DATA CUT SHEETS FOR THE NITROGEN GENERATOR
 SHOWN. FBC 107
 3. LABEL DRINKING FOUNTAIN TO BE GFCI PROTECTED PER NEC
 422.52
 4. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II