Plan Review Notes For Permit 15120875 |
Permit Number |
15120875 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-10 13:28:02 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE CLARIFY WHAT TYPE OF HEALTH FACILITY THIS IS. | | LAB TYPE. FBC 107 | | 2. PROVIDE DATA CUT SHEETS FOR THE NITROGEN GENERATOR | | SHOWN. FBC 107 | | 3. LABEL DRINKING FOUNTAIN TO BE GFCI PROTECTED PER NEC | | 422.52 | | 4. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. | | | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|