2016-01-09 03:59:20 | 1) VOID/REMOVE THE OLD PLANS FROM THE SET.SUBMIT ONLY 2 |
| SETS OF PLANS FOR REVIEW. ATTACH THE 8 1/2 X11 DRAWING |
| TO THE LARGE PLANS.WPB AMEND. TO FBC SEC. 107.2.1. |
| 2) THE REVISED GAS PLAN HAS THE ARCHITECT'S NAME & TILE |
| BLOCK ON THE PLANS. FLORIDA ADMINISTRATIVE CODE RULE |
| 61G1-16.001 REQUIRES THAT THE PLANS BE SIGNED AND |
| SEALED BY THE ARCHITECT OF RECORD. |
| 3) IS THE BBQ LOCATED IN AN OPEN AREA? IT IS DIFFICULT |
| TO TELL FROM THE SUBMITTED FLOOR PLAN. CLARIFY. |
| 4) THE PLANS SHOW THE COPPER LINE FOR THE BBQ TO BE |
| INSTALLED BELOW GROUND IN A SLEEVE.THE INSTALLATION FOR |
| THE PIPE AND SLEEVE SHALL COMPLY WITH 2014 FGC |
| SEC.404.14.1. |
| 5) THE USE OF COPPER TUBING FOR GAS PIPING HAS |
| LIMITATIONS PER FGC SEC.403.4.3 - COPPER AND BRASS. |
| COPPER AND BRASS PIPE SHALL NOT BE USED IF THE GAS |
| CONTAINS MORE THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN |
| SULFIDE PER 100 STANDARD CUBIC FEET OF GAS (0.7 |
| MILLIGRAMS PER 100 LITERS). THREADED COPPER, BRASS AND |
| ALUMINUM-ALLOY PIPE SHALL NOT BE USED WITH GASES |
| CORROSIVE TO SUCH MATERIALS. -SUBMIT VERIFICATION FROM |
| THE GAS PURVEYOR THAT THE GAS DOES NOT CONTAIN MORE |
| THAN 0.3 GRAINS OF HYDROGEN SULFIDE PER 100 STANDARD |
| CUBIC FEET OF GAS. |
| 6) THE FIREPLACE SHALL BE EQUIPPED WITH A FLAME |
| SAFEGUARD DEVICE PER 2014 FGC SEC.602.2 UNLESS THE THE |
| FIREPLACE HAS BEEN TESTED IN ACCORDANCE WITH ANSI |
| Z21.84. I COULD NOT FIND ANYTHING IN THE FIREPLACE |
| SPECIFICATIONS THAT NOTES IT HAS BEEN TESTED WITH |
| Z21.84. |
| 7) A YELLOW INSULATED TRACER WIRE SHALL BE INSTALLED |
| ADJACENT TO THE UNDERGROUND NONMETALLIC PIPING.2014 FGC |
| SEC.404.17.3. |
| 8) THE SUBMITTED PLAN HAS AN AREA SHOWN AS "2ND FLOOR |
| GAS PLAN" BUT THERE IS NO PIPNG SHOWN. IF GAS PIPE IS |
| NOT BEING RUN TO THIS AREA, NOTE THIS ON THE PLAN.WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| |
| NOTE: PRIOR TO RESUBMITTING CORRECTIONS, PLEASE ARRANGE |
| AN APPOINTMENT WITH ME SO WE CAN REVIEW THE CORRECTED |
| PLANS AND ENSURE ALL COMMENTS HAVE BEEN ADDRESSED. THIS |
| WILL HELP EXPEDITE YOUR PERMIT. |
| |