2016-01-09 03:59:201) VOID/REMOVE THE OLD PLANS FROM THE SET.SUBMIT ONLY 2
 SETS OF PLANS FOR REVIEW. ATTACH THE 8 1/2 X11 DRAWING
 TO THE LARGE PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE REVISED GAS PLAN HAS THE ARCHITECT'S NAME & TILE
 BLOCK ON THE PLANS. FLORIDA ADMINISTRATIVE CODE RULE
 61G1-16.001 REQUIRES THAT THE PLANS BE SIGNED AND
 SEALED BY THE ARCHITECT OF RECORD.
 3) IS THE BBQ LOCATED IN AN OPEN AREA? IT IS DIFFICULT
 TO TELL FROM THE SUBMITTED FLOOR PLAN. CLARIFY.
 4) THE PLANS SHOW THE COPPER LINE FOR THE BBQ TO BE
 INSTALLED BELOW GROUND IN A SLEEVE.THE INSTALLATION FOR
 THE PIPE AND SLEEVE SHALL COMPLY WITH 2014 FGC
 SEC.404.14.1.
 5) THE USE OF COPPER TUBING FOR GAS PIPING HAS
 LIMITATIONS PER FGC SEC.403.4.3 - COPPER AND BRASS.
 COPPER AND BRASS PIPE SHALL NOT BE USED IF THE GAS
 CONTAINS MORE THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN
 SULFIDE PER 100 STANDARD CUBIC FEET OF GAS (0.7
 MILLIGRAMS PER 100 LITERS). THREADED COPPER, BRASS AND
 ALUMINUM-ALLOY PIPE SHALL NOT BE USED WITH GASES
 CORROSIVE TO SUCH MATERIALS. -SUBMIT VERIFICATION FROM
 THE GAS PURVEYOR THAT THE GAS DOES NOT CONTAIN MORE
 THAN 0.3 GRAINS OF HYDROGEN SULFIDE PER 100 STANDARD
 CUBIC FEET OF GAS.
 6) THE FIREPLACE SHALL BE EQUIPPED WITH A FLAME
 SAFEGUARD DEVICE PER 2014 FGC SEC.602.2 UNLESS THE THE
 FIREPLACE HAS BEEN TESTED IN ACCORDANCE WITH ANSI
 Z21.84. I COULD NOT FIND ANYTHING IN THE FIREPLACE
 SPECIFICATIONS THAT NOTES IT HAS BEEN TESTED WITH
 Z21.84.
 7) A YELLOW INSULATED TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO THE UNDERGROUND NONMETALLIC PIPING.2014 FGC
 SEC.404.17.3.
 8) THE SUBMITTED PLAN HAS AN AREA SHOWN AS "2ND FLOOR
 GAS PLAN" BUT THERE IS NO PIPNG SHOWN. IF GAS PIPE IS
 NOT BEING RUN TO THIS AREA, NOTE THIS ON THE PLAN.WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 NOTE: PRIOR TO RESUBMITTING CORRECTIONS, PLEASE ARRANGE
 AN APPOINTMENT WITH ME SO WE CAN REVIEW THE CORRECTED
 PLANS AND ENSURE ALL COMMENTS HAVE BEEN ADDRESSED. THIS
 WILL HELP EXPEDITE YOUR PERMIT.
  