Plan Review Notes For Permit 15120860 |
Permit Number |
15120860 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-30 06:22:51 | 1. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE | | CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE | | (IF APPLICABLE). WPB AMENDMENTS TO FBC SEC.107.2.1. THE | | PLAN ONLY SHOWS THAT THE DROPS ARE GALVANIZED, WHAT | | TYPE OF PIPING IS THE REST OF THE ABOVEGROUND AND | | UNDERGROUND SYSTEMS? | | | | 2. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER | | OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE | | BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS | | SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. | | | | 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. | | SEC. G2413.2. . | | | | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | AND LABELED. | | | | 5) SHOW THE LOCATION OF ALL STEP DOWN REGULATORS ( IF | | APPLICABLE). WPB AMENDMENTS TO FBC SEC.107.2.1. | | | | 6) NOTE ON THE PLAN THE APPLICABLE SIZING TABLE(S) USED | | IN THE DESIGN OF THE GAS SYSYTEM FOR THE APPLICABLE | | PRESSURES. WPB AMENDMENTS TO FBC SEC.107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|