Plan Review Notes
Plan Review Notes For Permit 15120845
Permit Number 15120845
Review Stop M
Sequence Number 1
Notes
Date Text
2016-01-04 07:38:131ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120845
 01/04/15
  
 1) SHEET #2: THE LOUVERED DOOR AT THE AHU CLOSET CANNOT
 BE WOOD AS SPECIFIED IN THE SCHEDULE. IN ACCORDANCE
 WITH C403.2.7.2 FBC-14 ENERGY CONSERVATION AND SECTION
 602 FBC-14 MECHANICAL THE DOOR SHALL BE MADE OF
 NON-COMBUSTIBLE MATERIALS.
 2) SHEET #3: INDICATE A MEANS OF RETURN AIR FROM THE
 BEDROOM AND THE GUEST ROOM IN ACCORDANCE WITH SECTION
 601.5 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  