Plan Review Notes For Permit 15120845 |
Permit Number |
15120845 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-04 18:30:11 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | ALTERNATE CONTACT | | MIKE ALBARRAN | | 561-805-6746 | | [email protected] | | | | -FBC-ER 404.1.1 / 402.4.4 ( ADD TO NOTES ) | | RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT | | AS WELL AS IC RATED AND SEALED TO NOT COMPROMISE | | BUILDING THERMAL ENVELOPE. ( 2 CFM ) | | | | -PLEASE PROVIDE A PANEL SCHEDULE NEC 408.4A TO ENSURE | | THAT KITCHEN COUNTER TOP RECEPTACLES SHALL BE SUPPLIED | | BY NO FEWER THAN TWO SMALL APPLIANCE BRANCH CIRCUITS. | | NEC 210.52 B3 | | | | -SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS | | 314 & 315. VERIFY LOCATIONS TO THE FOLLOWING : | | SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE INSTALLED | | WITHIN A 36 IN. (910 MM) OF AC DUCTS AND HORIZONTAL | | PATH FROM A DOOR TO A BATHROOM CONTAINING A SHOWER OR | | TUB UNLESS LISTED FOR INSTALLATION IN CLOSE PROXIMITY | | TO SUCH LOCATIONS. RELOCATE THE UNITS ACCORDINGLY. |
|