2016-02-04 18:30:111ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 -FBC-ER 404.1.1 / 402.4.4 ( ADD TO NOTES )
 RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT
 AS WELL AS IC RATED AND SEALED TO NOT COMPROMISE
 BUILDING THERMAL ENVELOPE. ( 2 CFM )
  
 -PLEASE PROVIDE A PANEL SCHEDULE NEC 408.4A TO ENSURE
 THAT KITCHEN COUNTER TOP RECEPTACLES SHALL BE SUPPLIED
 BY NO FEWER THAN TWO SMALL APPLIANCE BRANCH CIRCUITS.
 NEC 210.52 B3
  
 -SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS
 314 & 315. VERIFY LOCATIONS TO THE FOLLOWING :
 SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE INSTALLED
 WITHIN A 36 IN. (910 MM) OF AC DUCTS AND HORIZONTAL
 PATH FROM A DOOR TO A BATHROOM CONTAINING A SHOWER OR
 TUB UNLESS LISTED FOR INSTALLATION IN CLOSE PROXIMITY
 TO SUCH LOCATIONS. RELOCATE THE UNITS ACCORDINGLY.