Plan Review Notes For Permit 15120821 |
Permit Number |
15120821 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-02-23 13:36:38 | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | FAC 61G20-3.002(33) FOR: | | A) UNDERLAYMENT SPECIFIED ON PLANS FOR THE OPEN | | BALCONY. UNDERLAYMENT TO BE DESIGNED TO RECEIVE TILE AS | | SPECIFIED ON PLANS. NOTE: SIGNED AND SEALED RAS 117 | | CALCULATIONS MAY BE REQUIRED IF THE PRODUCT APPROVAL | | SUBMITTED DOESN'T MEET THE ARCHITECT'S CALCULATED | | DESIGN PRESSURES. | | RESPONSE: CERTAIN TEED MODIFIED BITUMEN NOA 14-0224.03 | | SUBMITTED IS NOT DESIGNED TO RECEIVE TILE FLOORING. | | THIS PRODUCT IS FOR FLAT ROOF SYSTEMS ONLY. ON THE | | OTHER HAND, THE DESIGN PRESSURES FOR SELECTED SYSTEM ON | | SHEET 15 OF 16 ARE TOO LOW. GENERAL LIMITATION #7 ON | | LAST PAGE OF NOA SUBMITTED REQUIRES RAS 117 | | CALCULATIONS TO MEET THE CALCULATED DESIGN PRESSURES. | | NEED TO PROVIDE PRODUCT APPROVAL DESIGNED TO RECEIVE | | FLOOR TILE AND SIGNED AND SEALED RAS 117 CALCULATIONS | | MAY BE REQUIRED. | | | | B) PROVIDE PRODUCT APPROVAL FOR THE ROOF TILE | | UNDERLAYMENT SPECIFIED BY THE ARCHITECT ON SHEETS 8 AND | | 9. NOTE: UNDERLAYMENT NEEDS TO LIST THE ROOF TILE | | ADHESIVE PRODUCT APPROVAL SUBMITTED. (UNDERLAYMENT | | SPECIFIED ON SHEETS 8 AND 9 LOOKS MORE LIKE A PRODUCT | | USED FOR FLAT ROOFS ASSEMBLIES NOT FOR ROOF TILE | | UNDERLAYMENTS). | | | | 2- ARCHITECT OF RECORD TO APPROVE ABOVE PRODUCT | | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY | | AMENDMENTS. | | |
|