Notes
Date Text
2016-02-23 13:36:38 
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) UNDERLAYMENT SPECIFIED ON PLANS FOR THE OPEN
 BALCONY. UNDERLAYMENT TO BE DESIGNED TO RECEIVE TILE AS
 SPECIFIED ON PLANS. NOTE: SIGNED AND SEALED RAS 117
 CALCULATIONS MAY BE REQUIRED IF THE PRODUCT APPROVAL
 SUBMITTED DOESN'T MEET THE ARCHITECT'S CALCULATED
 DESIGN PRESSURES.
 RESPONSE: CERTAIN TEED MODIFIED BITUMEN NOA 14-0224.03
 SUBMITTED IS NOT DESIGNED TO RECEIVE TILE FLOORING.
 THIS PRODUCT IS FOR FLAT ROOF SYSTEMS ONLY. ON THE
 OTHER HAND, THE DESIGN PRESSURES FOR SELECTED SYSTEM ON
 SHEET 15 OF 16 ARE TOO LOW. GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA SUBMITTED REQUIRES RAS 117
 CALCULATIONS TO MEET THE CALCULATED DESIGN PRESSURES.
 NEED TO PROVIDE PRODUCT APPROVAL DESIGNED TO RECEIVE
 FLOOR TILE AND SIGNED AND SEALED RAS 117 CALCULATIONS
 MAY BE REQUIRED.
  
 B) PROVIDE PRODUCT APPROVAL FOR THE ROOF TILE
 UNDERLAYMENT SPECIFIED BY THE ARCHITECT ON SHEETS 8 AND
 9. NOTE: UNDERLAYMENT NEEDS TO LIST THE ROOF TILE
 ADHESIVE PRODUCT APPROVAL SUBMITTED. (UNDERLAYMENT
 SPECIFIED ON SHEETS 8 AND 9 LOOKS MORE LIKE A PRODUCT
 USED FOR FLAT ROOFS ASSEMBLIES NOT FOR ROOF TILE
 UNDERLAYMENTS).
  
 2- ARCHITECT OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  