Date |
Text |
2016-01-20 18:42:45 | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC-5TH EDITION (2014). |
| |
| 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| CODE. |
| |
| 2- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 3- PROVIDE DRAINAGE PLAN (2 COPIES). SEC. R401.3 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 4- SPECIFY THE ATTIC LIVE LOAD AS REQUIRED BY |
| FOOT-NOTES "B" AND "G" OF TABLE R301.5 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). CLEARLY SPECIFY |
| THE LIVE LOADS FOR THE TRUSSES TO HAVE STORAGE AND FOR |
| THE TRUSSES WITHOUT STORAGE. SEE FOOT-NOTES. |
| |
| 5- DOOR LEADING FROM THE GARAGE TO THE MAIN HOUSE. |
| PROVIDE SPECIFICATIONS FOR SELF CLOSING DOOR AS |
| REQUIRED BY SEC. R302.5.1 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| 6- THERE ARE SOME WINDOWS ON THE SECOND FLOOR WITH THE |
| WINDOW SILL LOCATED LESS THAN 24" FROM THE FINISHED |
| FLOOR. NEED TO PROVIDE COMPLIANCE WITH THE WINDOW FALL |
| PROTECTION AS REQUIRED BY SEC. R312.2 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). CLEARLY IDENTIFY |
| ON PLANS ALL WINDOWS WITH A SILL LESS THAN 24" FROM THE |
| FLOOR AND PROVIDE COMPLIANCE WITH THE WINDOW FALL |
| PROTECTION. |
| |
| 7- A) PROVIDE CONNECTION DETAIL AT BOTH ENDS OF 24" D |
| FL. GDR SHOWN ON SHEET 4 TO SUPPORT THE LOFT ABOVE. |
| SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| B) SPECIFY COLUMN AT BOTH ENDS OF OF FL. GDR ABOVE. |
| SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 8- LEDGER ANCHORING SPECIFICATIONS SHOWN ON LEDGER |
| ANCHORING NOTES ON SHEET 5 DON'T MATCH SPECIFICATIONS |
| SHOWN ON 2 STORY WALL SECTION SHOWN ON SHEET 8. REVISE |
| AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 9- NAILING SCHEDULE ON SHEET 5: |
| A) REVISE NAILING SPACING FOR ROOF ZONE #3 TO COMPLY |
| WITH SEC. R803.2.3.1 OF FBC-RESIDENTIAL, 5TH EDITION |
| (2014). |
| |
| B) REVISE NAIL SIZE SPECIFIED FOR THE CEILING AND |
| SOFFIT METAL LATH. NAIL NEEDS TO HAVE 1-3/4" |
| PENETRATION INTO THE HORIZONTAL FRAMING MEMBER. A |
| 1-1/2" NAIL DOESN'T PROVIDE THE REQUIRED MIN. |
| EMBEDMENT. SEE ASTM C-1063 AND REVISE AS REQUIRED. |
| |
| 10- DESIGN PARAMETERS INFORMATION ON SHEET 5: CLARIFY |
| WHAT IS THE .7 DEAD LOAD REDUCTION FACTOR FOR?. WHERE |
| IN THE CODE IS THIS REDUCTION ALLOWED?. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| 11- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING |
| METHOD AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. |
| IF USING ADHESIVE, THEN PROVIDE PRODUCT APPROVAL. IF |
| USING NAILS, THEN SPECIFY TYPE, SIZE AND NUMBER OF |
| NAILS. |
| |
| 12- SPECIFICATIONS ON GARAGE DOOR ANCHOR DETAIL ON |
| SHEET 3 DON'T MATCH SPECIFICATIONS ON GARAGE DOOR |
| ATTACHMENT ON SHEET 6. REVISE AS REQUIRED TO MATCH. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 13- UPDATE FLASHING SPECIFICATIONS ON THE WINDOW DETAIL |
| ON SHEET 6. THE CURRENT CODE IS THE FBC-RESIDENTIAL, |
| 5TH EDITION (2014) NOT 2010 FBC. |
| |
| 14- UPDATE CODE SECTIONS SPECIFIED ON THE INTERIOR |
| RAILING DETAIL AND INTERIOR STAIR DETAIL ON SHEET 6. |
| ALSO, UPDATE INFORMATION SHOWN ON RAILING DETAIL ON |
| SHEET 9. SEE FBC-RESIDENTIAL, 5TH EDITION (2014) FOR |
| CORRECT CODE SECTIONS AND REVISE AS REQUIRED. |
| |
| 15- GUARDRAIL SHOWN ON THE OPEN BALCONY ON REAR |
| ELEVATION ON SHEET 6 DOESN'T COMPLY WITH THE OPENING |
| LIMITATIONS OF SEC. R312.1.3 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). REVISE AS REQUIRED. PROVIDE DIMENSIONS |
| FOR ALL OPENINGS ON THE DESIGN SHOWN. |
| |
| 16- UPDATE THE CODES AND STANDARDS INFORMATION ON SHEET |
| 7. THE CURRENT CODE IS THE FBC-5TH EDITION (2014). |
| |
| 17- WALL SECTIONS ON SHEET 8: SPECIFY THE CLEARANCE |
| BETWEEN THE EXTERIOR WALL COVERING AND FINAL EARTH |
| GRADE AS REQUIRED BY SEC. R318.7 OF FBC-RESIDENTIAL, |
| 5TH EDITION (2014). |
| |
| 18- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) FIBERGLASS DOOR THAT MEETTS THE DESIGN PRESSURES |
| CALCULATED BY THE ARCHITECT. FLORIDA PRODUCT APPROVAL |
| FL15037.3 SUBMITTED DOESN'T MEET THE CALCULATED DESIGN |
| PRESSURES. |
| |
| B) FRENCH DOORS THAT MEETS THE DESIGN PRESSURES |
| CALCULATED BY THE ARCHITECT. FLORIDA PRODUCT APPROVAL |
| FL7630.4 SUBMITTED DOESN'T MEET THE CALCULATED DESIGN |
| PRESSURES. |
| |
| C) OVERHEAD GARAGE DOORS THAT MEETS THE DESIGN |
| PRESSURES CALCULATED BY THE ARCHITECT. FLORIDA PRODUCT |
| APPROVAL FL16107-R8 SUBMITTED DOESN'T MEET THE |
| CALCULATED DESIGN PRESSURES. |
| |
| D) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF |
| RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED |
| ADHESIVES. |
| |
| E) SINGLE HUNG WINDOWS THAT MEETS THE DESIGN PRESSURES |
| CALCULATED BY THE ARCHITECT. NOA 15-0519.08 SUBMITTED |
| DOESN'T MEET THE CALCULATED DESIGN PRESSURES. |
| |
| F) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| G) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| LIST THE FLORIDA PRODUCT APPROVAL NUMBER ON EACH |
| SPECIFIED CONNECTOR ON PLANS. |
| |
| H) ALL SHUTTERS SHOWN ON FRONT ELEVATION. AND, PROVIDE |
| COMPLETE INSTALLATION SCHEDULE. |
| |
| I) UNDERLAYMENT SPECIFIED ON PLANS FOR THE OPEN |
| BALCONY. UNDERLAYMENT TO BE DESIGNED TO RECEIVE TILE AS |
| SPECIFIED ON PLANS. NOTE: SIGNED AND SEALED RAS 117 |
| CALCULATIONS MAY BE REQUIRED IF THE PRODUCT APPROVAL |
| SUBMITTED DOESN'T MEET THE ARCHITECT'S CALCULATED |
| DESIGN PRESSURES. |
| |
| 19- ARCHITECT OF RECORD TO APPROVE IN WRITING (NOT |
| SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 20- ICYNENE INSULATION SPECIFIED ON PLANS: PROVIDE |
| ICYNENE ICC EVALUATION REPORT. AND ARCHITECT TO REVIEW |
| AND APPROVE PRIOR TO SUBMITTAL. SEC. R316 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 21- CLARIFY WHY SUBMITTING A FLOOD ZONE ELEVATION |
| CERTIFICATE. THIS PROPERTY IS NOT LOCATED IN A FLOOD |
| ZONE. PROPERTY IS LOCATED IN FLOOD ZONE "C". ELEVATION |
| CERTIFICATE IS NOT REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD |
| DRAWINGS. SUBMITT OLD DRAWINGS FOR REFERENCE. |
| |