2015-12-29 14:44:361) SHOW THE BTU OF THE TANKLESS WATER HEATER. THE
 MANUF. SPECS. SHOW A RANGE OF A BTU LOAD. IT APPEARS
 THESE ARE 199,000 BTU LOAD WATER HEATERS. CLARIFY.
 2) TABLE 402.4 (5) IS FOR A 2 PSI SYSYTEM BUT THE PSI
 SHOWN ON THE RISER DIAGRAM IS 5 PSI. CLARIFY.
 3) INDICATE ON THE PLANS HOW THE PIPING IS GOING TO BE
 SUPPORTED. COMPLY WITH 2014 FGC SEC.415 & TABLE 415.1.
 4)