2016-01-06 13:51:25 | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS | | | | 1.PROVIDE PLUMBING RISER DIAGRAM WATER AND SANITARY PER | | WPB AMEND TO FBC SEC107.3.5.1.3(13) | | 2. YOUR PRIMARY OCCUPANCY IS ASSEMBLY A1 NOT BUSINESS | | PER FBC 303.2 | | 3. YOUR OCCUPANT LOAD SHALL BE CALCULATED BY USING THE | | DIFFERENT AREAS PRESCRIBED IN FBC TABLE 1004 .2.1 | | ASSEMBLY FIXED SEAT ,ASSEMBLY WITHOUT FIXED SEATS | | STANDING ROOM 5 NET ,STAGES AND PLATFORMS 15 NET AND | | BUSINESS | | ALL THESE AREAS MUST BE CALCULATED SEPARATELY. | | 4. A DRINKING FOUNTAIN COMPILING WITH FBC PL SEC410.2 | | IS REQUIRED PER FBC PL TABLE 403.1 | | 5. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1 |
|