2015-12-29 13:17:31 | 1ST REVIEW 2014 MECHANICAL |
| PERMIT #15120750 |
| 12/29/15 |
| |
| 1) PROVIDE AC COOLING AND HEATING LOAD CALCULATIONS IN |
| COMPLIANCE WITH SECTION C403.2.1 FBC-14 ENERGY |
| CONSERVATION. |
| 2) THE OUTSIDE AIR CALCULATIONS ARE NOT IN COMPLIANCE |
| WITH ASHRAE 62.1 OR TABLE 403.3 FBC-14 MECHANICAL. THE |
| OCCUPANT DENSITY IS CALCULATED AT 150 PER 1000 SF. FOR |
| THE AUDITORIUM AREA WHICH COMPRISES APPROXIMATELY 752 |
| SF. USING A SCALE RULER (PLAN DOES NOT PROVIDE |
| DIMENSIONS). I AM CALCULATING 112 PEOPLE AT 5 CFM'S |
| EACH= 564 + 45 CFM'S FOR A TOTAL OF 609 CFRMS. THIS |
| AMOUNT MUST BE ADDED TO THE O/A CFM'S REQUIRED FOR THE |
| BACK OFFICE/WORK, AND THE FOYER AREAS. |
| 3) M2.1: PROVIDE THE DIMENSIONS OF THE RETURN AIR GRILL |
| AT THE AC CLOSET- SEE SECTION 601.5. |
| 4) M2.1: THE TRANSFER DUCT IS UNDERSIZED PER SECTION |
| 601.5 |
| 5) M2.1: THE AC CLOSET IS CONSIDERED A PLENUM CHAMBER |
| PER SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION. |
| PLEASE INDICATE THE TYPE OF DOOR TO BE INSTALLED AT THE |
| CLOSET- REFER TO SECTION 602 FBC-14 MECHANCIAL. |
| 6) M4.01: PROVIDE THE CURRENT WIND LOAD DESIGN CRITERIA |
| AND WIND SPEED FOR INSTALLATION OF THE AC ROOF STAND- |
| SEE SECTION 301.15 FBC-14 MECHANICAL. SUBMIT TWO COPIES |
| OF THE ROOF STAND NOA REVIEWED AND APPROVED BY THE |
| E.O.R. |
| 7) M2.01: UNLESS A MINIMUM 42" HIGH PARAPET WALL IS |
| EXISTING ABOVE THE ROOF, GUARDS MUST BE INSTALLED IN |
| ACCORDANCE WITH SECTION 304.11 FBC-14 MECHANICAL. |
| 8) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR |
| SYSTEMS OF AC SYSTEMS WITH A DESIGN CAPACITY GREATER |
| THAN 2000 CFM. IF THE CARRIER SYSTEM CAN PRODUCE MORE |
| THAN 2000 CFMS IT MUST BE IN COMPLIANCE. PLEASE PROVIDE |
| A CUT SHEET FROM THE MANUFACTURER. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |
| |