Plan Review Notes For Permit 15120750 |
Permit Number |
15120750 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-31 10:31:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. SHEET A0.10 - THE OCCUPANCY LOAD CALCULATIONS ARE | | INCORRECT. THE OFFICE AREA CAN BE CALCULATED AS | | BUSINESS; HOWEVER, THE STAGE, VIEWING AND FRONT AREA | | SHALL BE CALCULATED AS ASSEMBLY, WHICH EXCEEDS THE | | INDICATED OCCUPANCY LOAD. | | | | 2. SHEET A3.00 - THERE IS NO INDICATION OF DOOR | | HARDWARE OR LOCKING/LATCHING MECHANISMS. THE OCCUPANCY | | LOAD CALCULATIONS SHALL REQUIRE PANIC HARDWARE AND | | LOCKING/LATCHING ON ALL EXIT DOORS PER NFPA 101, | | CHAPTER 7, MEANS OF EGRESS. | | | | 3. SHEET A1.01 - A CURTAIN WALL IS INDICATED TOWARDS | | THE FRONT OF THE OCCUPANCY. THIS CURTAIN IS NOT | | APPROVED AND CANNOT IMPEDE THE EXIT TRAVEL PATH AND | | MEANS OF EGRESS. AN EXIT SPACE SHALL BE CLEARLY | | INDICATED AND BE ILLUMINATED BY AN EXXIT SIGN. THE | | CURTAIN WALL SHALL BE FLAME RETARDENT AND MEET ALL THE | | REQUIREMENTS OF FLAME SPREAD AND SMOKE PROPAGATION PER | | NFPA 101. |
|