Plan Review Notes
Plan Review Notes For Permit 15120750
Permit Number 15120750
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-12-31 10:31:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1. SHEET A0.10 - THE OCCUPANCY LOAD CALCULATIONS ARE
 INCORRECT. THE OFFICE AREA CAN BE CALCULATED AS
 BUSINESS; HOWEVER, THE STAGE, VIEWING AND FRONT AREA
 SHALL BE CALCULATED AS ASSEMBLY, WHICH EXCEEDS THE
 INDICATED OCCUPANCY LOAD.
  
 2. SHEET A3.00 - THERE IS NO INDICATION OF DOOR
 HARDWARE OR LOCKING/LATCHING MECHANISMS. THE OCCUPANCY
 LOAD CALCULATIONS SHALL REQUIRE PANIC HARDWARE AND
 LOCKING/LATCHING ON ALL EXIT DOORS PER NFPA 101,
 CHAPTER 7, MEANS OF EGRESS.
  
 3. SHEET A1.01 - A CURTAIN WALL IS INDICATED TOWARDS
 THE FRONT OF THE OCCUPANCY. THIS CURTAIN IS NOT
 APPROVED AND CANNOT IMPEDE THE EXIT TRAVEL PATH AND
 MEANS OF EGRESS. AN EXIT SPACE SHALL BE CLEARLY
 INDICATED AND BE ILLUMINATED BY AN EXXIT SIGN. THE
 CURTAIN WALL SHALL BE FLAME RETARDENT AND MEET ALL THE
 REQUIREMENTS OF FLAME SPREAD AND SMOKE PROPAGATION PER
 NFPA 101.