2016-02-08 15:44:49JOB PERMIT NUMBER: 15120750
 JOB ADDRESS: 811 A BELVEDERE RD
 WEST PALM BEACH
 DATE: FEB 8 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1 NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20
 AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET
 LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF
 WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL
 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING
 RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE
 ?WR?. THIS APPLIES TO THE CU UNIT UP ON THE ROOF.
 2 NEC 210.8 GFCI PROTECTION ??. (B) OTHER THAN DWELLING
 UNITS. AS FAR AS THE STAGE PERFORMANCE AREA RECEPTACLES
 WERE PORTABLE LIGHTING EQUIPMENT ARE TO BE USED.
 3 NO LIGHTING CONTROLS IN OFFICE AREA PLEASE SEE FBC-E
 C405 AS A REFERENCE
 4 FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 5 GENERAL NOTES STATE THAT A FIXTURE MOUNTING DETAIL
 SHALL BE FOUND IN ARCHITECTURAL ELEVATION? COULDN'T
 FIND !
 6 NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED
 7 PROVIDE ARC FLASH AND AVAILABLE FAULT CURRENT FIELD
 LABELING NEC 110.16 / 110.24
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER