2016-02-08 15:44:49 | JOB PERMIT NUMBER: 15120750 |
| JOB ADDRESS: 811 A BELVEDERE RD |
| WEST PALM BEACH |
| DATE: FEB 8 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| 1 NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING |
| RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| ?WR?. THIS APPLIES TO THE CU UNIT UP ON THE ROOF. |
| 2 NEC 210.8 GFCI PROTECTION ??. (B) OTHER THAN DWELLING |
| UNITS. AS FAR AS THE STAGE PERFORMANCE AREA RECEPTACLES |
| WERE PORTABLE LIGHTING EQUIPMENT ARE TO BE USED. |
| 3 NO LIGHTING CONTROLS IN OFFICE AREA PLEASE SEE FBC-E |
| C405 AS A REFERENCE |
| 4 FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| CONDITIONED & UNCONDITIONED SPACES. |
| 5 GENERAL NOTES STATE THAT A FIXTURE MOUNTING DETAIL |
| SHALL BE FOUND IN ARCHITECTURAL ELEVATION? COULDN'T |
| FIND ! |
| 6 NEC 250.94 BONDING FOR OTHER SYSTEMS. THE |
| INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| INSTALLED |
| 7 PROVIDE ARC FLASH AND AVAILABLE FAULT CURRENT FIELD |
| LABELING NEC 110.16 / 110.24 |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |