2016-01-09 08:00:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120750
 ADD: 811A BELVEDERE RD.
 CONT: TBD
 TEL: 305-710-7178
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI., JAN. 08/2016
 ACTION: DENIED
  
 1) SHEET A0.10 UNDER THE BUILDING CODE SUMMARY;
  
 1A) DISCREPANCY IN PLANS THE TOTAL PROJECT AREA IS
 STATED IN THE PLANS 1682 SQ. FT. THE BUILDING SCALE
 INDICATES 1/8 INCH / FOOT THE TOTAL OVERALL SQUARE FEET
 IS OVER 6580 SQUARE FEET. GOOGLE SHOWS FOR LEASE SIGNS
 WITH 1800 =/- SQUARE FEET. PLEASE CORRECT THE
 DISCREPANCIES IN THE PLAN. 107.2.1.3.
  
 1B) THE BUILDING CODE SUMMARY LIST THIS ALTERATION AS A
 LEVEL 3, A LEVEL 3 ALTERATION PER THE 2014 FBC-EXISTING
 BUILDING CODE 505.1 SCOPE. LEVEL 3 ALTERATIONS APPLY
 WHERE THE WORK AREA EXCEEDS 50 PERCENT OF THE AGGREGATE
 AREA OF THE BUILDING. PLEASE PROVIDE WHERE 50 % OF THE
 FLOOR AREA IS BEING ALTERED? THIS BUILDING APPEARS TO
 BE A PARTIAL CHANGE OF OCCUPANCY AND WOULD NEED TO
 COMPLY WITH 2014 FBC-EXISTING BLDG. CODE 1001.3.1
 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION. WHERE A
 PORTION OF AN EXISTING BUILDING IS CHANGED TO A NEW
 OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 1C) PLEASE BREAK DOWN THE AREAS OF OCCUPANCY BY SQUARE
 FOOTAGE AND OCCUPANT LOADS FOR EACH USE AREA. THE PLANS
 INDICATE A BUSINESS OCCUPANCY OF 1682/100= 17 OCCUPANTS
 . THE OFFICE/ WORKROOM IS ONLY 462 SQ. FT. OR A
 OCCUPANT LOAD OF 5. FOR BOTH THE A1 THEATER AND THE A3
 PLACE OF WORSHIP THE OCCUPANT LOAD IS FIGURED AT 15
 SQUARE FEET PER OCCUPANT (NET) PER FBC-B TABLE
 1004.1.2. PLEASE PROVIDE THE TOTAL SQUARE FOOTAGE OF
 THE BUILDING AND OCCUPANT LOAD.
  
 1D) PLEASE SHOW THE MEANS OF EGRESS PATH NOT AS A
 SINGLE LINE BUT THE WIDTH OF THE MEANS OF EGRESS AND
 OCCUPANT LOADS. THIS SQUARE FOOTAGE CAN BE DELETED FROM
 THE TOTAL SQUARE FOOTAGE AS WELL AS THE RESTROOMS AND
 WALLS (NET) SEE CHAPTER 2 DEFINITIONS.
  
 1E) PLEASE PROVIDE ADDITIONAL DETAIL AS TO THE USAGE OF
 THE OFFICE / WORK ROOM. PLEASE DEFINE WHAT ACTIVITIES
 WILL BE TAKING PLACE IN THE WORK ROOM. THE SECOND MEANS
 OF EGRESS IS THROUGH THE WORK ROOM.
 COMPLIANCE WITH THE 2914 FBC-B 1014.2 EGRESS THROUGH
 INTERVENING SPACES WILL NEED TO BE PROVIDED AS TO THE
 ALLOWABLE USAGE OF THE ROOM, AND A DEMARCATED PATH
 CLEAR OF FURNITURE AND OR OBSTACLES.
  
 2) SHEET A0.10 SHOWS WHAT APPEARS TO BE A CURTAIN HUNG
 ACROSS WHAT APPEARS TO BE A PRE-FUNCTION AREA AND THE
 MAIN ASSEMBLY OCCUPANCY. PLEASE SHOW COMPLIANCE WITH
 2014 FBC-B 1008.1 MEANS OF EGRESS DOORS SHALL BE
 READILY DISTINGUISHABLE FROM THE ADJACENT CONSTRUCTION
 AND FINISHES SUCH THAT THE DOORS ARE EASILY
 RECOGNIZABLE AS DOORS. MIRRORS OR SIMILAR REFLECTING
 MATERIALS SHALL NOT BE USED ON MEANS OF EGRESS DOORS.
 MEANS OF EGRESS DOORS SHALL NOT BE CONCEALED BY
 CURTAINS, DRAPES, DECORATIONS OR SIMILAR MATERIALS.
  
 3) SHEET A0.10 LIST THE FRONT AREA OF THE THEATER AS A
 LOBBY. IS THIS AREA TO BE CONSIDERED A PRE-FUNCTION
 AREA WHERE PERSONS ARE ADMITTED TO THE BUILDING AT
 TIMES WHEN SEATS ARE NOT AVAILABLE, SUCH PERSONS SHALL
 BE ALLOWED TO WAIT IN A LOBBY OR SIMILAR SPACE,
 PROVIDED SUCH LOBBY OR SIMILAR SPACE SHALL NOT ENCROACH
 UPON THE REQUIRED CLEAR WIDTH OF THE MEANS OF EGRESS.
 SUCH FOYER, IF NOT DIRECTLY CONNECTED TO A PUBLIC
 STREET BY ALL THE MAIN ENTRANCES OR EXITS, SHALL HAVE A
 STRAIGHT AND UNOBSTRUCTED CORRIDOR OR PATH OF TRAVEL TO
 EVERY SUCH MAIN ENTRANCE OR EXIT. 1028.3.
  
 4) THE PLANS FAIL TO PROVIDE AN ACCESSIBLE CIRCULATION
 PATH, ACCESSIBLE SEATING AND COMPANION SEATING. 2014
 FBC-ACCESSIBILITY CODE:
  
 206.2.6 PERFORMANCE AREAS. WHERE A CIRCULATION PATH
 DIRECTLY CONNECTS A PERFORMANCE AREA TO AN ASSEMBLY
 SEATING AREA, AN ACCESSIBLE ROUTE SHALL DIRECTLY
 CONNECT THE ASSEMBLY SEATING AREA WITH THE PERFORMANCE
 AREA. AN ACCESSIBLE ROUTE SHALL BE PROVIDED FROM
 PERFORMANCE AREAS TO ANCILLARY AREAS OR FACILITIES USED
 BY PERFORMERS UNLESS EXEMPTED BY 206.2.3 EXCEPTIONS 1
 THROUGH 7.
  
 802.2 LINES OF SIGHT. LINES OF SIGHT TO THE SCREEN,
 PERFORMANCE AREA, OR PLAYING FIELD FOR SPECTATORS IN
 WHEELCHAIR SPACES SHALL COMPLY WITH 802.2.
  
 802.3 COMPANION SEATS. COMPANION SEATS SHALL COMPLY
 WITH 802.3.
  
 802.3.1 ALIGNMENT. IN ROW SEATING, COMPANION SEATS
 SHALL BE LOCATED TO PROVIDE SHOULDER ALIGNMENT WITH
 ADJACENT WHEELCHAIR SPACES. THE SHOULDER ALIGNMENT
 POINT OF THE WHEELCHAIR SPACE SHALL BE MEASURED 36
 INCHES (915 MM) FROM THE FRONT OF THE WHEELCHAIR SPACE.
 THE FLOOR SURFACE OF THE COMPANION SEAT SHALL BE AT THE
 SAME ELEVATION AS THE FLOOR SURFACE OF THE WHEELCHAIR
 SPACE.
  
 802.3.2 TYPE. COMPANION SEATS SHALL BE EQUIVALENT IN
 SIZE, QUALITY, COMFORT, AND AMENITIES TO THE SEATING IN
 THE IMMEDIATE AREA. COMPANION SEATS SHALL BE PERMITTED
 TO BE MOVABLE.
  
 802.4 DESIGNATED AISLE SEATS. DESIGNATED AISLE SEATS
 SHALL COMPLY WITH 802.4.
  
 5) SHEET M2.01:
  
 5A) THIS SHEET SHOWS A NEW ROOF TOP A/C CONDENSER ON A
 NEW ROOF TOP A/C STAND. PLEASE SHOW COMPLIANCE WITH
 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31(G) PRE-ENGINEERED A/C STANDS
  
 PLEASE ALSO REVIEW TABLE 1509.6.5 FBC-B CLEARANCES
 BELOW RAISED ROOF MOUNTED MECHANICAL UNITS.
  
 5B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5C) PLEASE PROVIDE THE WIND DESIGN IN COMPLIANCE WITH:
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5C) 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 5C)2. RISK CATEGORY.
  
 5C)3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 5C)4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5C)5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5D) PLEASE PROVIDE WHAT ADDITIONAL TYPE OF
 REINFORCEMENT OF THE ROOF FRAMING SYSTEM (MAIN WIND
 FORCE RESISTING SYSTEM) MWFRS WILL THE ENGINEERED A/C
 STAND ANCHOR TOO? FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 5E) PLEASE ALSO PROVIDE THE METHOD OF ATTACHMENT OF THE
 A/C CONDENSER TO THE ROOF TOP STAND. FBC-B 1609.6.4.4.1
 COMPONENTS & CLADDING.
  
 5F) NONE OF THE PLANS PROVIDE A SECTION THROUGH THE
 EXTERIOR WALL INDICATING IF THERE IS A PARAPET WALL
 LOCATED NEXT TO THE A/C ROOF TOP CONDENSER. PLEASE SHOW
 COMPLIANCE WITH :
 2014 FBC- 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL BE
 PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF HATCH
 OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE
 LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN
 SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO
 AS TO PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533
 MM) IN DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN
 30 INCHES (762 MM) BEYOND EACH END OF SUCH APPLIANCE,
 EQUIPMENT, FAN OR COMPONENT.
  
 6) IMPACT FEES: BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  