Plan Review Notes
Plan Review Notes For Permit 15120707
Permit Number 15120707
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-14 10:09:201ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 PROVISO : FACP B IN MECHANICAL ROOM DOESN'T HAVE A
 SMOKE DETECTOR PLEASE INSTALL PRIOIR TO INSPECTION.
 NFPA 72 2010 EDTION 10.15* PROTECTION OF FIRE ALARM
 SYSTEM. IN AREAS THAT ARE NOT
 CONTINUOUSLY OCCUPIED, AUTOMATIC SMOKE DETECTION SHALL
 BE
 PROVIDED AT THE LOCATION OF EACH FIRE ALARM CONTROL
 UNIT(S),
 NOTIFICATION APPLIANCE CIRCUIT POWER EXTENDERS, AND
 SUPERVISING
 STATION TRANSMITTING EQUIPMENT TO PROVIDE NOTIFICATION
 OF
 FIRE AT THAT LOCATION.