Plan Review Notes For Permit 15120707 |
Permit Number |
15120707 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-14 10:09:20 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6700 | | [email protected] | | ALTERNATE CONTACT | | MIKE ALBARRAN | | 561-805-6746 | | [email protected] | | | | PROVISO : FACP B IN MECHANICAL ROOM DOESN'T HAVE A | | SMOKE DETECTOR PLEASE INSTALL PRIOIR TO INSPECTION. | | NFPA 72 2010 EDTION 10.15* PROTECTION OF FIRE ALARM | | SYSTEM. IN AREAS THAT ARE NOT | | CONTINUOUSLY OCCUPIED, AUTOMATIC SMOKE DETECTION SHALL | | BE | | PROVIDED AT THE LOCATION OF EACH FIRE ALARM CONTROL | | UNIT(S), | | NOTIFICATION APPLIANCE CIRCUIT POWER EXTENDERS, AND | | SUPERVISING | | STATION TRANSMITTING EQUIPMENT TO PROVIDE NOTIFICATION | | OF | | FIRE AT THAT LOCATION. |
|